BACnet Objects
Object_Name
Default
ID
name
Writeable
BV:0
Reserved for VFD profile
RUN/STOP
BV:1
Command
x
REF 1/REF 2
BV:2
Select
x
Fault Reset
BV:3
Command
x
RUN/STOP
BV:4
Monitor
x
OK/FAULT
BV:5
Monitor
x
HAND/AUTO
BV:6
Reference
x
BV:7
BV:8
BV:9
BV:10
BV:11
BV:12
BV:13
Reserved for VFD profile
BV:14
BV:15
BV:16
BV:17
BV:18
BV:19
BV:20
BV:21
Warning
x
BV:22
Trip
x
BV:23
Triplock
BV:24
Coasting
BV:25
CW/CCW
BV:26
Jog
BV:27
Reset
Reset KWh
BV:28
Counter
Reset
Running
Hours
BV:29
Counter
Speed =
BV:31
reference
BV:32
Bus control
BV:33
Running
x
Ramp 1/
BV:34
Ramp 2
Table 5.7 Binary Values
®
VLT
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
Bit
EEPROM Parameter
number
CTW=0x47C
+
Reversing
x
bit 15
6 reverse 15 x
x
Note 1
n/a
x
CTW
7
x
STW
1
x
STW
3, 6, 7
x
16-95
1
x
STW
7
x
STW
3
STW
6
CTW
3
CTW
15
CTW
8
CTW
7
1506
n/a
1507
n/a
STW
8
STW
9
x
STW
11
CTW
9
MG03O102 - Danfoss A/S © 12/2013. All rights reserved.
Present_Value
Writeable
Cmd.able
EEPROM
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Timeout
x
x
5
5
x
x
x
x
17