Danfoss DriveMotor FCP 106 BACnet Operating Instructions Manual page 17

Hide thumbs Also See for DriveMotor FCP 106 BACnet:
Table of Contents

Advertisement

BACnet Objects
Object_Name
Default
ID
name
Writeable
Running
AV:22
Hours
AV:23
kWh Counter
Motor
AV:24
Voltage
AV:25
Frequency
DC Link
AV:27
Voltage
Heatsink
AV:28
Temp.
Inverter
AV:29
Thermal
Bus Feedback
AV:31
1
AV:32
Reserved for P, I
AV:33
AV:37
AV:38
Reserved for P, I
AV:39
AV:42
AV:43
Reserved for P, I
AV:44
AV:46
AV:47
AV:48
AV:49
Alarm Log:
AV:50
Error Code
AV:51
Fault Code
PID Start
AV:52
Speed
On Reference
AV:53
Bandwidth
PID Propor-
AV:54
tional Gain
PID Integral
AV:55
Time
Table 5.3 Analog Values
1)
Either AV:1 or AV:2 controls the frequency converter
reference. Only one of them can control the frequency
converter at a time and BV:2 decides which one.
2)
This value is not directly available in the frequency
converter. The value must be calculated as follows:
Par . 16 − 13
AV # 3 =
× 100%
Par . 4 − 14
3)
This value is not directly available in the frequency
converter. The value must be calculated as follows:
Par . 16 − 52
AV # 4 =
× 100%
Par . 3 − 03
®
VLT
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
EEPROM
Parameter
1501
1502
1612
1613
1630
1634
1635
894
1530
4)
2083
2084
2093
2094
4)
analog value in AV:51. The fault codes are mapped as
shown in Table 5.4. The frequency converter alarm codes
are shown as well for comparison.
Table 5.4 shows the mapping of the frequency converter
alarm codes and their mapping to the BACnet's fault
codes.
MG03O102 - Danfoss A/S © 12/2013. All rights reserved.
Present_Value
Unit
Writeable
Hours
kWh
V
Hz
V
ºC
%
N
x
2
NONE
NONE
Hz
x
%
x
NONE
x
S
x
Frequency converter fault codes are transmitted as an
Cmd.able
Timeout
15
5
5