Danfoss DriveMotor FCP 106 BACnet Operating Instructions Manual page 18

Hide thumbs Also See for DriveMotor FCP 106 BACnet:
Table of Contents

Advertisement

BACnet Objects
Fault codes
Communication Error
Over Current
Over Temperature
Over Speed Deviation
Over Voltage
Under Voltage
Short Circuit
5
5
Ground Fault
Motor Overload
Inverter Overload
Over Torque Detection
External Fault
Operator Interface Error
Load Loss
Configuration Error
Feedback Failure
Output Phase Loss
Motor Stall
Power Unit Error
Input Phase/DC Ripple
Internal Drive Failure
Table 5.4 Mapping of Fault Codes
5.1.2 Binary Input and Output Objects
ID
BI:2
BI:3
BI:4
BI:5
BI:10..BI:15 are reserved for P1660/x
Table 5.5 Binary Inputs
Object_Name
ID
Default name
BO:4
Relay 1
BO:5
Relay 2
Table 5.6 Binary Outputs
16
VLT
Fault code
Frequency converter alarms
1
17
2
59
3
69
4
N.A.
5
7
6
8
7
16
8
14
9
10
10
9
11
N.A.
12
2, 24, 43, 60, 63,
13
46, 47, 50, 51, 52, 53, 54, 55, 56,
57, 58
14
93, 94, 95
15
40, 41
16
N.A.
17
30, 31, 32
18
11
19
N.A.
20
4
21
38
Object_Name
Default name
Digital input Term 29
Digital input Term 27
Digital input Term 19
Digital input Term 18
Parameter
590
590
MG03O102 - Danfoss A/S © 12/2013. All rights reserved.
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
Parameter
1660
1660
1660
1660
Bit number
4
5
Fault descriptions
Loss of communication with the network
Instantaneous output current has exceeded
frequency converter rated or programmed value
Heat sink temperature limit has been reached
N.A.
DC link voltage has exceeded frequency converter
limit
DC link voltage is lower than required frequency
converter limit
Frequency converter output has shorted phase-to-
phase
Frequency converter output grounding current has
exceeded manufacturer limitations
Motor is overloaded
Timed over current fault
N.A.
External fault has been activated in the frequency
converter. This is a hard fault that must be reset.
Inverter programming or operational interface
malfunction
Load on the Motor is less than programmed limit
of system. An Example is a broken belt or coupling
Errors exist in the programmed or operational
configuration of the inverter
N.A.
One or more of the output phases from the
inverter to the motor are open
Motor is operating in stall region and not able to
accelerate
N.A.
Input single phase or low line voltage condition
Manufacturer defined internal operations that have
failed their-self checks.
Present_Value
Bit number
2
3
4
5
Present_Value
Writeable
Cmd.able
x
x
x
x
Timeout
x
x