3 Operation

3.1 Flame simulator activation

•Testing using a flame simulator to simulate a fire to the detector may activate alarms
or extinguishing systems in the area unless disabled/inhibited/bypassed.
•All tests should be coordinated, and if needed, disconnect/disable the alarm
and/or the extinguishing systems before the test, and reconnect after the test.
1. Remove simulator from the case and verify the simulator battery is charged.
2. Ensure use of the correct flame simulator model according to the detector type.
3. Make sure you are testing within the specified distance, according to the detector sensitivity.
See Table 1 below.
4. Point the flame simulator at center of detector by aligning the front and back aiming sights
located on the top of the simulator (3).
5. The simulator should be aimed within +/- 30⁰ from the horizontal and vertical center line axis of
the detector.
6. Press the push button (4) to activate, notice the flashing green LED. Wait for the flame detector
to enter into alarm (typically 10 seconds). Go to the next detector and repeat the test.