FIRST START ASSISTANT

Initial start-up has been performed at the factory. Use of the start
up assistant will override factory VFD configurations.
CAUTION
CONFIGURATION OVERRIDE HAZARD
Do not use start-up assistant on this VFD application! Use of
start-up assistant will override the factory VFD configurations!
Use the following procedure to reset the factory configurations for
ACH580 VFDs:
1.
Disconnect unit power. Lock-out/tag-out.
2.
Remove the VFD's front cover.
3.
Disconnect the DI1 input at Terminal 13 (see Fig. 38 for
location of DI1).
Digital Input
Terminals
13 – 18
Fig. 38 — Digital Input Terminal Block Location on
ACH580 VFD
4.
Connect the VFD Keypad accessory to the VFD (if not
already connected).
NOTE: The VFD Keypad is a field-installed accessory; it is
not included with the factory-installed VFD option.
5.
At this point, providing you have a clean backup of the
drive, you can select "RESTORE" from "BACKUP"
Menu from the Main Menu.
Please Note: To restore a backup, the drive has to be in
Local control.
6.
If you do not have a clean backup the drive will have to be
manually programmed following the instructions in this
document.
7.
When the correct parameters have been uploaded, discon-
nect power to the unit, reconnect DI1 to Terminal 13, and
replace the VFD cover.
8.
Reconnect power to the unit. The VFD is now commis-
sioned from the backup file.
START UP BY CHANGING PARAMETERS 
INDIVIDUALLY
Initial start-up is performed at the factory. To start up the VFD by
changing individual parameters, perform the following procedure:
1.
Select MENU (Press
2.
Use the UP or DOWN keys to highlight PARAMETERS
on the display screen and press ENTER (Press
3.
Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (Press
4.
Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (Press
5.
Use the UP or DOWN keys to change the value of the
parameter.
6.
Press SAVE (Press
Press CANCEL (Press
Any modifications that are not saved will not be changed.
7.
Choose another parameter or press EXIT/BACK (Press
) to return to the listing of parameter groups. Con-
tinue until all the parameters have been configured and
then press EXIT/BACK (Press
menu.
NOTE: The current parameter value appears above the highlight
parameter. To view the default parameter value, press the UP and
DOWN keys simultaneously.

ACH580 VFD Modes

The VFD has several different modes for configuring, operating,
and diagnosing the VFD. The modes are:
Standard Display mode — shows drive status information
and operates the drive.
Parameters mode — edits parameter values individually.
Start-up Assistant mode — guides the start up and
configuration.
Changed Parameters mode — shows all changed parameters.
Drive Parameter Backup mode — stores or uploads the pa-
rameters.
Clock Set mode — sets the time and date for the drive.
I/O Settings mode — checks and edits the I/O settings.

ACH580 STANDARD DISPLAY MODE

Use the standard display mode to read information on the drive
status and operate the drive. To reach the standard display mode,
press BACK until the LCD display shows status information as
described below. (See Fig. 39.)
The top line of the LCD display shows the basic status informa-
tion of the drive. The HAND icon indicates that the drive control
is local from the control panel. The AUTO icon indicates that the
drive is in remote control mode, such as the basic I/O or field bus.
The arrow icon indicates the drive and motor rotation status. A ro-
tating arrow (clockwise or counterclockwise) indicates that the
drive is running and at set point and the shaft direction is forward
or reverse. A rotating blinking arrow indicates that the drive is
running but not at set point. A stationary arrow indicates that the
drive is stopped. For the units covered in this manual, the correct
display rotation is clockwise.
The upper right corner shows the frequency set point that the drive
will maintain.From Home view press "Options" then "Edit Home
View" to change the Home layout, the middle of the LCD display
can be configured to display 3 parameter values, Graphs or digital
indicators. The default display shows (OUTPUT FREQ) in per-
cent speed, (CURRENT) in amperes, and (Al1) in voltage DC.
The bottom corners of the LCD display show the functions cur-
rently assigned to the two soft keys. The lower middle displays the
current time (if configured to show the time).
34
). The Main menu is displayed.
).
).
).
) to store the modified value.
) to keep the previous value.
) to return to the main

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crdiskit003a00

Table of Contents