The first time the drive is powered up, it is in the OFF mode. To
switch to local hand-held control and control the drive using the
control panel, press and hold the HAND button. Pressing the
HAND button switches the drive to hand control while keeping
the drive running. Press the AUTO button to switch to remote in-
put control. To start the drive press the HAND or AUTO buttons,
to stop the drive press the OFF button.
Fig. 39 — ACH580 Standard Display Example
The top line of the LCD display shows the basic status informa-
tion of the drive. The HAND icon indicates that the drive control
is local from the control panel. The AUTO icon indicates that the
drive is in remote control mode, such as the basic I/O or field bus.
The arrow icon indicates the drive and motor rotation status. A ro-
tating arrow (clockwise or counterclockwise) indicates that the
drive is running and at set point and the shaft direction is forward
or reverse. A rotating blinking arrow indicates that the drive is
running but not at set point. A stationary arrow indicates that the
drive is stopped. For the units covered in this manual, the correct
display rotation is clockwise.
The upper right corner shows the frequency set point that the drive
will maintain.
From Home view press "Options" then "Edit Home View" to
change the Home layout, the middle of the LCD display can be
configured to display 3 parameter values, Graphs or digital
indicators. The default display shows (OUTPUT FREQ) in per-
cent speed, (CURRENT) in amperes, and (Al1) in voltage DC.
The bottom corners of the LCD display show the functions cur-
rently assigned to the two soft keys. The lower middle displays the
current time (if configured to show the time).
The first time the drive is powered up, it is in the OFF mode. To
switch to local hand-held control and control the drive using the
control panel, press and hold the HAND button. Pressing the
HAND button switches the drive to hand control while keeping
the drive running. Press the AUTO button to switch to remote in-
put control. To start the drive press the HAND or AUTO buttons,
to stop the drive press the OFF button.
To adjust the speed in HAND mode, press the UP or DOWN but-
tons (the reference changes immediately). The reference can be
modified in the local control (HAND) mode, and can be parame-
terized (using Group 11 reference select) to also allow modifica-
tion in the remote control mode.

PARAMETERS MODE

The Parameters mode is used to change the parameters on the
drive. To change parameters, perform the following procedure:
1.
Select MENU (Press
displayed.
2.
Use the UP or DOWN keys to highlight PARAMETERS on
the display screen and press Select (Press
3.
Use the UP or DOWN keys to highlight the desired
parameter group and press Select (Press
4.
Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (Press
5.
Use the UP or DOWN keys to change the value of the
parameter.
6.
Press SAVE (Press
CANCEL (Press
modifications that are not saved will not be changed.
7.
Choose another parameter or press BACK (Press
return to the listing of parameter groups. Continue until all the
parameters have been configured and then press EXIT (Press
) to return to the main menu.

CHANGED PARAMETERS MODE

The Changed Parameters mode is used to view and edit recently
changed parameters on the drive. To view the changed parameters,
perform the following procedure:
1.
Select MENU (Press
displayed.
2.
Use the UP or DOWN keys to highlight PARAMETERS on
the display screen and press Select (Press
3.
Use the UP or DOWN keys to highlight MODIFIED on the
display screen and press Select (Press
recently changed parameters will be displayed.
4.
Use the UP or DOWN keys to highlight the desired
parameter group and press EDIT (Press
the parameter if desired.
5.
Press BACK (Press
mode.

DRIVE PARAMETER BACKUP MODE

The drive parameter back up mode is used to export the parame-
ters from one drive to another. The parameters can be uploaded
from a VFD to the removable control panel. The control panel can
then be transferred to another drive and the parameters download-
ed into memory.
Depending on the motor and application, there are two options
available. The first option is to download all parameters. This cop-
ies both application and motor parameters to the drive from the
control panel. This is recommended when using the same applica-
tion for drives of the same size. This can also be used to create a
backup of the parameters group for the drive.
The second option downloads only the application parameters to
the drive. This is recommended when using the same application
for drives of different sizes. Parameters 99.07, 99.06, 99.08, 99.09,
99.10, and group 51 parameters and internal motor parameters are
not copied.
Upload All Parameters
To upload and store parameters in the control panel from the VFD
insert the Keypad into the VFD slot (Fig. 40) and animation will
appear loading the VFD configuration.
35
). The Main menu will be
).
).
).
) to store the modified value. Press
) to keep the previous value. Any
). The Main menu will be
).
). A list of the
) to change
) to exit the Changed Parameters