The following table describes the components to be configured in the 4G LTE scenario.
Location
Component
LAN switch (optional) UT-H605 or ES1000
Smart array
Fitting
controller
bags for
the POE
Outside the
module
smart array
and
controller
customer-
and box-
premises
type
equipment
transformer
(CPE)
MCB
Box-type
Three-
transformer
phase
power
switch
Select either an MCCB or a knife fuse switch as the three-phase power switch. If you select an
MCCB, ensure that the let-through energy of the MCCB meets requirements. The breaking
capacity depends on the limited short-circuit current on the low voltage side of the box-type
transformer.
Models of the components inside the box-type transformer are specified by the box-type
transformer vendor.
Recommended Model or
Specifications
POE
N/A
module
CPE
N/A
Recommended rated current: 32 A;
number of poles: 2
When the rated AC voltage on
the low-voltage side of the box-
type transformer is less than or
equal to 500 V, the rated voltage
of the knife fuse switch should be
greater than or equal to 600 V.
When the rated AC voltage on
Knife fuse
the low-voltage side of the box-
switch
type transformer is greater than
(solution
500 V and less than or equal to
1)
800 V, the rated voltage of the
knife fuse switch should be
greater than or equal to 800 V.
Recommended rated current of
the fuse: 32 A; rated current of
the knife fuse switch box ≥ 32 A;
number of poles: 3 (3 fuses for
each knife fuse switch box)
When the rated AC voltage on
the low-voltage side of the box-
type transformer is less than or
equal to 500 V, the rated voltage
of the molded case circuit
breaker (MCCB) should be
greater than or equal to 600 V.
When the rated AC voltage on
MCCB
the low-voltage side of the box-
(solution
type transformer is greater than
2)
500 V and less than or equal to
800 V, the rated voltage of the
MCCB should be greater than or
equal to 800 V.
Let-through energy ≤ 1.26 x 10
2
A
s
Recommended rated current: 32
A; number of poles: 3
6
8
Component
Quantity
Source
1
1
1
Can be
purchased
from Huawei
1
1
Scenario
with a
double-
column
Prepared by
transformer:
the customer
1
Scenario
with a dual-
split
transformer:
2