The following table describes the cables to be prepared by yourself in the fiber ring networking scenario.
No. Cable
Three-phase AC
1
power cable
Peripheral
2
network cable
Peripheral
RS485
3
communications
cable
Cabinet PE
4
cable
5
Optical cable
Single-phase AC
6
power cable
24 V DC input
7
and output
power cables
Recommended Model or Specifications
Four-core (L1, L2, L3, and functional earthing)
outdoor copper armored cable with three OT-M6
terminals (L1, L2, and L3) and one OT-M4
terminal (functional earthing)
When the rated AC voltage on the low-voltage
side of the box-type transformer is less than or
equal to 500 V, the operating voltage between
the three-phase AC power cable and the ground
should be greater than or equal to 600 V.
When the rated AC voltage on the low-voltage
side of the box-type transformer is greater than
500 V and less than or equal to 800 V, the
operating voltage between the three-phase AC
power cable and the ground should be greater
than or equal to 1000 V.
CAT 5E outdoor shielded network cable with an
outer diameter less than 9 mm (0.35 in.) and internal
resistance not greater than 1.5 ohms/10 m (1.5
ohms/32.81 ft), as well as a shielded RJ45
connector
A computer cable (DJYP2VP2-22 2x2x1) or armored
shielded twisted pair that can be used outdoors and
OT-M4 terminals
Outdoor copper cable with an OT-M6 terminal
Four-core or eight-core single-mode armored optical
cable with a transmission wavelength of 1310 nm
and an outer diameter less than or equal to 18 mm
(0.71 in.)
Common connection: one two-core outdoor
copper armored cable
Connection through a tube: two single-core
outdoor copper cables
Operating voltage to the ground ≥ 300 V
Common connection: one two-core outdoor
copper armored cable
Connection through a tube: two single-core
outdoor copper cables
Operating voltage to the ground ≥ 300 V
6
Cross-sectional Area
Range of the Cable
(Recommended)
2
8–10 mm
(10 mm
8 AWG
N/A
2
2
0.5–1 mm
(1 mm
20–18 AWG (18 AWG)
2
6–16 mm
(16 mm
10–6 AWG (6 AWG)
N/A
2
2
4–6 mm
(4 mm
)
12–10 AWG (12 AWG)
2
2.5–4 mm
(2.5 mm
14–12 AWG (14 AWG)
2
)
)
2
)
2
)