Installing/Mounting; Installation Instructions Sitrans Cc220; Mounting Sitrans Cc220 - Siemens SITRANS SCM IQ Operating Instructions Manual

Smart condition monitoring with iiot sensors
Hide thumbs Also See for SITRANS SCM IQ:
Table of Contents

Advertisement

Installing/mounting

5.1

Installation instructions SITRANS CC220

5.1.1

Mounting SITRANS CC220

Introduction
• Observe the safety notes in chapter Notes on use (Page 18).
• The device is approved for indoor operation only.
• Install the device in cabinets, separate rooms or controlled areas. Only authorized personnel
may access the device using locks or similar measures.
• Observe the relevant DIN/VDE requirements or the applicable country-specific regulations.
• Install the bluetooth antenna outside the cabinet.
• To install the mounting clamps and brackets, Siemens recommends you use 0.6 Nm
tightening torque.
Before mounting the device
You have all needed anchors and screws available.
Material
Concrete
Plasterboard,
(at least 13 mm thick)
Metal,
(at least 2 mm thick)
Procedure
1. Mount the device on DIN rails or wall.
Mounting positions and mounting types (Page 27)
Mounting on DIN rails (Page 30)
Vertical wall mounting (Page 31)
2. Only mount by Siemens delivered bluetooth antenna.
3. Mount the bluetooth antenna outside the cabinet.
SITRANS SCM IQ: Smart Condition Monitoring with IIoT Sensors
Operating Instructions, 07/2023, A5E50573389-AD
Bore diameter
Select according to the specifi‐
cation of the mounting ele‐
ments used
Fixing element
Anchor, ∅ 6 mm, 40 mm long
Screw, ∅ 4.5 mm, 40 mm long
Toggle plug, ∅ 12 mm, 50 mm long
Screw M4 × 15
M4 nut
5
25