F14 Zero Cut-Off Setting - SMC Networks ISE70 AB Series Operation Manual

High-precision digital pressure switch
Hide thumbs Also See for ISE70 AB Series:
Table of Contents

Advertisement

■[F14] Zero cut-off setting
When the pressure display value is close to zero, the product rounds the value and zero will be displayed.
The zero cut-off range is 0.0 to 10.0% F.S., and can be set in 1.0% F.S. increments.
<Operation>
Press the UP or DOWN button in function selection mode to display [F14].
Select zero cut-off setting
Press the UP or DOWN button to select the value of zero cut-off.
: The display above is an example of when [MPa] is selected for the ISE70 (1 MPa range) with the unit switching function.
: When the actual pressure is smaller than the displayed value in the upper line, zero will be displayed.
Example: 1 MPa range P_1 = 0.015 [MPa], H_1 = 0.01 [MPa], zero cut-off 1.0%
Press the SET button to set.
Press the SET button.
[F14] Zero cut-off setting completed
-43-
Move on to select zero cut-off setting.
Return to function selection mode.
No.PS※※-OMW0002-D