PR 9100 Series Manual page 17

Temperature/ma converter
Table of Contents

Advertisement

Input error - check input connection and reset power
Output error - check output connections and reset power
No communication
Flash memory error - check configuration
Invalid configuration type or version
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
Hardware error
!
All error indications in the display flash once per second. The help text explains the error.
* Error is acknowledged by either stepping through the basic setup, or by resetting the device power.
Some types of errors can only be acknowledged by resetting the device power.
** Error is acknowledged by either stepping through the basic setup, or by resetting the device power.
Error can be disregarded by selecting input type different than TC.
***
Error is acknowledged by stepping through the basic setup.
Readout at hardware error
Error search
9113 - Product Version 9113-004
Readout
Signal levels on input beyond
IN.ER
limits or connected to wrong
terminals*
Error in analogue output
AO.ER
current (SIL mode only)*
No communication with
NO.CO
FL.ER
FLASH error (configuration
CO.ER
invalid)***
Configuration read from
TY.ER
EEprom has invalid type or
RA.ER
RAM error*
IF.ER
Internal Flash error*
SW.ER
SW monitor error*
AD.ER
A/D converter error*
AO.SU
Analogue output supply error*
CA.ER
Factory calibration error*
CM.ER
Main CPU error*
II.ER
Initialisation check error*
RS.ER
Reset error*
IC.ER
Input communication error*
M1.ER
Main CPU to Ch.1 error*
M2.ER
Main CPU to Ch.2 error*
MC.ER
Main CPU config. error*
MF.ER
Main CPU Flash error*
MR.ER
Main CPU RAM error*
MS.ER
Main CPU supply error*
MP.ER
Main CPU ProgFlow error*
Cause