Clearances To Heat-Sensitive Materials; Location Of The Certification Label; Clearances To Walls And Ceiling - Enerzone Solution 1.6 Installation And Operation Manual

Table of Contents

Advertisement

7 CLEARANCES TO HEAT-SENSITIVE MATERIALS

It is of utmost importance that the clearances to heat-sensitive materials be carefully maintained
upon installation of the wood fire you have selected. Refer to the tables below.
No part of the wood fire or flue may be located closer to combustibles than the minimum
clearance figures given.

7.1 LOCATION OF THE CERTIFICATION LABEL

Since the information given on the certification label affixed to the appliance always overrides the
information published, in any other media (owner's manual, catalogues, flyers, magazines and/or
web sites) it is important to refer to it in order to have a safe and compliant installation. In
addition, you will find information about your wood fire (model, serial number, etc.). You can find
the certification label on the back of the wood fire.

7.2 CLEARANCES TO WALLS AND CEILING

WHERE THE FLUE PASSES THROUGH A WALL, CEILING, FLOOR OR ROOFS, VENTILATED DOUBLE
FLUE-WOOD FIRE CASINGS MUST BE USED AROUND THE FLUE, ALONG WITH CEILING PLATES
AS SPECIFIED IN AS/NZS 2918:2001. THE CASING SHALL PASS THROUGH THE ENTIRE THICKNESS
OF WALL, CEILING OR WALL.
See figure Clearances to heat sensitive materials and floor protection to match each letter to a
clearance.
 Bottom of appliance to ceiling height must be at least 2,400 mm in all cases.
 The clearance between the flue and a wall are valid only for vertical walls and for vertical
flue.
Solution 1.6 Installation and Operation Manual
CLEARANCES
A
110 mm
B
250 mm
C
150 mm
F
1 m
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eb00037

Table of Contents