Figure 12: Example Binary Outputs and the
Associated Source Power Jumper Positions
Universal Input Current Loop Jumpers
The Universal Input (UI) current loop fail-safe jumpers
are on the circuit board under the controller cover near
the UI terminals
(Figure
10). When a UI is defined (in the
system software) as a 4-20 mA Analog Input and the UI's
current loop jumper is in the Disabled (default) position
(Figure
13), the 4-20 mA current loop circuit opens
whenever power to the controller is interrupted or off.
Figure 13: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position
(Figure
13) connects an internal 100 ohm resistor across
the UI terminals, which maintains the 4-20 mA current
loop circuit even when power to the controller is
interrupted or off.
Important: Current Loop jumpers must be in the
Disabled (default) position for all UIs that
are not set up to operate as 4-20 mA analog
inputs.
FEC26Field Equipment Controllers Installation Instructions
All manuals and user guides at all-guides.com
Table 7
with each UI on the FEC26 controller.
Table 7: FEC26 UI Inputs and Jumper Labels
Universal Input
Label
IN1
IN2
IN3
IN4
IN5
IN6
Setting Up an Integral or Local
Display
FEC2621x models have an integral LCD and push button
user interface that allows you to set up and monitor the
FEC, the FEC I/O points, and the modules and I/O points
connected on the SA bus. FEC2621 models do not have
an integral display, but can be connected to a DIS1710
Local Controller Display. For detailed information on
setting up and operating either an integral user interface
or a remotely connected DIS1710 display, refer to the
DIS1710 Local Controller Display Technical Bulletin
(LIT-12011270).

Commissioning Field Controllers

You commission field controllers with the Controller
Configuration Tool (CCT) software, via a Bluetooth®
Wireless Commissioning Converter, a USB dongle with
ZigBee®, Ethernet connection, or in BACnet router mode
when connected to an NAE or NCE. Refer to the
Controller Tool Help (LIT-12011147) for detailed
information on commissioning controllers.

Troubleshooting Field Controllers

Observe the Status LEDs on the front of the field
controller and see
To troubleshoot an integral or local controller display,
refer to the DIS1710 Local Controller Display Technical
Bulletin (LIT-12011270).
identifies the current loop jumpers associated
Jumper Label on Circuit Board
J20
J21
J22
J23
J24
J25
Table 8
to troubleshoot the controller.