Danfoss Optyma iCO2 Instructions Manual page 52

Packaged condensing unit
Hide thumbs Also See for Optyma iCO2:
Table of Contents

Advertisement

Instructions
Rated Specifications
Item
Power source
Power input
Current
Conditions
1. Evaporating temperature: -10 °C
2. Ambient temperature: 32 °C
3. Suction superheat : 10K
Performances (380 V / 400 V / 415 V)
Model : OP-UPAC015COP04E
Refrigerant fluid : R744
Ambient Temperature
Parameter
Evaporating temperature
Application
Suction super heat
Sub cooling
Annual electricity consumption
Seasonal Energy Performance Ratio
Rated cooling capacity
32 °C
Rated power input
Rated COP
Rated cooling capacity
25 °C
Rated power input
Rated COP
Rated cooling capacity
15 °C
Rated power input
Rated COP
Rated cooling capacity
5 °C
Rated power input
Rated COP
Rated cooling capacity
43 °C
Rated power input
Rated COP
Capacity control
Degradation coefficient for fixed and staged units
Sound pressure level
The A-weighted sound pressure level does not exceed 70 dB(A).
(at a distance of 1 m from surface of product)
52 | AN405821998738en-000102 - 118A5495A
Rating
3-phase, 380/400/415 V, 50 Hz
10.54/10.54/10.54
17.4/16.5/15.9
Symbol
t
e
Q
SEPR
P
A
D
A
COP
A
P
B
D
B
COP
B
P
C
D
C
COP
C
P
D
D
D
COP
D
P
3
D
3
COP
3
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Unit
V
kW
A
Values
-10
-35
MBP
LBP
10
10
0
0
30535
43818
3.95
1.74
19.60
10.20
10.54
10.39
1.86
0.98
17.57
9.67
6.92
7.65
2.54
1.26
14.66
8.92
4.01
5.37
3.65
1.66
11.76
8.16
2.09
3.90
5.63
2.09
15.82
8.44
10.99
10.68
1.44
0.79
Step / Variable
0.25
Unit
°C
K
K
kWh/a
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW