• Connect it to the terminal board using M3.5 crimp terminal as shown in the sketch below.
7 mm or less
• Use an adequate screwdriver to tighten terminal screws. If it is tightened too much, it could destroy screws. For the tightening torque of screw, see the
table below.
M3.5
8 – Filling the system
• Never start the compressor under vacuum. Keep the compressor switched off.
• Use only the refrigerant for which the unit is designed for.
• Break vacuum with 7 - 10 bar of vapor CO2.
• Then fill refrigerant in liquid phase through the medium pressure access port.
• The remaining charge is done until the installation has reached a level of stable nominal condition during operation.
• Never leave the filling cylinder connected to the circuit.