Installation and User Guide
O4
#2 Set On Time
O5
#2 Set PR Period (max . 900 minutes)
W4
Channel #2 > Alarm Temps & En/Dis
O6
#2 Alarm Temp En/Dis
O7
#2 Alarm min . Temp
O8
#2 Alarm max . Temp
W5
Channel #2 > CableOK?
O9
#2 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
O10
#2 CableOK? = NO/NC . Set up DI2 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
W75
Power calculator > Channel Power #2
O11
#2 Channel Power (max . 32000)
W8
Channel #2 > Manually On/Of
O12
#2 Manually On/Of Time – Set up period of time
for MOn or MOf status (max . 900 minutes)
O13
#2 Status On or Of for mode Heating Manually
O14
#2 Manually On/Of Start or Stop control mode .
Caution: this mode may cause overheating and
damage!
W9
Channel #2 > Channel ON/OFF
O15
#2 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp . is
being shown
W11
Channel #2 > Sensor type
O17
#2 Sensor type
W12
Channel #2 > Relay Status RO/RC
O18
#2 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status 'Heating On'
W13
Channel #2 > Relay Test 5/30 sec .
O19
#2 Relay Test 5/30 - Every 5 sec . switching for 30 sec .
R1
Channel #3 > Regulation Type
I1
#3 Regulation Type: 1S – Single Sensor,
PR – Power Regulation
R2
Channel #3 > Temp & Hysteresis
I2
#3 Set Temperature
I3
#3 Set +-Hysteresis
R3
Channel #3 > On Time & Period
I4
#3 Set On Time
I5
#3 Set PR Period (max . 900 minutes)
R4
Channel #3 > Alarm Temps & En/Dis
I6
#3 Alarm Temp En/Dis
I7
#3 Alarm min . Temp
I8
#3 Alarm max . Temp
FEC | Produced by Danfoss ©
DEVIreg™ Multi
1
0
0
900
0
1
-50
0
0
200
0
1
0
1
0
32000
1
900
0
1
0
1
0
1
0
7
0
1
0
1
0
1
-50
200
0 .2
6
1
0
0
900
0
1
-50
0
0
200
15
min .
30
min .
0 – Dis
Enum 5
0
°C
60
°C
0 – Dis
Enum 5
1 – NO
Enum 8
0
W
1
min .
0 – Of
Enum 11
0 – STOP
Enum 6
0 – OFF
Enum 7
1 – PT1000
Enum 9
0 – RC
Enum 10
0 – STOP
Enum 6
1 – 1S
Enum 1
5
°C
0 .4
°C
15
min .
30
min .
0 – Dis
Enum 5
0
60
RW
3029
RW
3030
RW
3031
RW
3032
RW
3033
RW
3034
RW
3035
RW
3036
RW
3037
RW
3038
RW
3039
RW
3040
RW
3041
RW
3042
RW
3043
RW
3044
RW
3045
RW
3046
RW
3047
RW
3048
RW
3049
RW
3050
RW
3051
39
Need help?
Do you have a question about the 140F1139 and is the answer not in the manual?