Starting The Inverters - Huawei UPS2000-H Quick Manual

Hide thumbs Also See for UPS2000-H:
Table of Contents

Advertisement

UPS2000-H-(6 kVA-10 kVA)
Quick Guide

2.2.2.2 Starting the Inverters

Prerequisites
1.
2.
Procedure
Step 1 If the alarm indicator on the UPS panel is blinking, view the alarm details on the
app and handle the alarm.
Step 2 Choose Config > Quick Settings.
1.
2.
Issue 03 (2023-08-20)
The UPSs have been powered on.
You have installed and logged in to the app.
Set the voltage level and frequency level based on site requirements.
Set the battery type, single battery voltage, number of batteries in a battery
string, single battery capacity, and number of battery strings based on site
requirements.
Figure 2-16 Quick Settings
Table 2-2 Quick Settings
Item
Description
Voltage
Specifies the system output
level(V)
voltage level. This
parameter is configurable
only after the inverter is
shut down.
Frequency
Specifies the system output
level(Hz)
frequency level. This
parameter is configurable
only after the inverter is
shut down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On Commissioning
Setting
Value Range
Set as
220, 230, and
required.
240. The
default value
is 220.
Set as
50, 60, and
required.
automatic.
The default
value is 50.
60