8. Technical Specifications

Quattro-II
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
INVERTER
DC Input voltage range
Output when in inverter mode
Cont. output power at 25°C (3)
Cont. output power at 25°C
Cont. output power at 40°C
Cont. output power at 65°C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
Maximum output current
CHARGER
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
GENERAL
Auxiliary output
Programmable relay (5)
Protection (2)
VE.Bus communication port
General purpose communication port
Remote on-off
Operating temperature range
Humidity (non-condensing)
ENCLOSURE
Material & Colour
Protection category
Battery-connection
120/240 V AC-connection
Page 26
Quattro-II 2x120V
12/3000/120-50 2x120V
Yes (on L1 input)
50 A (each leg)
9.5 – 17 V
Output voltage: 120 VAC ± 2%
Frequency: 60 Hz ± 0.1% (1)
3000 VA
2400 W
2200 W
1700 W
2500 VA
5500 W
93%
15 W
10 W
4 W
60A peak, 50Arms for 1seconds
Split phase: 180-280 VAC 45 – 65 Hz
Single phase: 90-140 VAC 45 – 65 Hz
14.4 V
13.8 V
13.2 V
120 A
Yes (50 A)
For parallel and three phase operation, remote monitoring and system
integration
Yes, 2x
-40 to +65°C (-40 - 150°F) fan assisted cooling
max 95%
Steel, blue RAL 5012
2x2 M8 bolts
Screw terminals 21 mm² (4 AWG)
24/3000/70-50 2x120V
50 A
19 - 33 V
94%
11 W
8 W
4 W
28.8 V
27.6 V
26.4 V
70 A
Yes
Yes
a – g
Yes
IP22
2 M8 bolts
Technical Specifications

Advertisement

Table of Contents
loading

Table of Contents