Technical Specifications - Victron energy MultiPlus-II 230V Manual

Table of Contents

Advertisement

8. Technical Specifications

MultiPlus-II
PowerControl / PowerAssist
AC input
Maximum feed through current
INVERTER
Input voltage range
Output (1)
Cont. output power at
25 °C / 77 °F (3)
Cont. output power at
25 °C / 77 °F
Cont. output power at
40 °C / 104 °F
Cont. output power at
65 °C / 150 °F
Maximum feed-in power
Peak power
Maximum efficiency
Zero-load power
Zero-load power in AES mode
Zero-load power in Search
mode
CHARGER
AC input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Charge current house
battery (4)
GENERAL
Auxiliary output
External AC current sensor
(optional)
Programmable relay (5)
Protection (2)
VE.Bus communication port
General purpose com. port
Page 26
MultiPlus-II 230V
12/3000/120-32
24/3000/70-32
Yes
Input voltage range: 187-265 VAC
32 A
9.5 – 17 V
19 – 33 V
Output voltage: 230 VAC ± 2 %
3000 VA
2400 W
2200 W
1700 W
3000 VA
5500 W
93 %
94 %
13 W
13 W
9 W
9 W
3 W
3 W
Input voltage range: 187-265 VAC
Input frequency: 45 – 65 Hz
Power factor: 1
14.4 / 28.8 / 57.6 V
13.8 / 27.6 / 55.2 V
13.2 / 26.4 / 52.8 V
120 A
70 A
Yes (32 A)
Default setting: switches off
when in inverter mode
50 A
Yes
a - g
For parallel and three phase operation, remote monitoring and
system integration
Yes, 2x
48/3000/35-32
Input frequency: 45 – 65 Hz
38 – 66 V
Frequency: 50 Hz ± 0,1 %
95 %
11 W
7 W
2 W
35 A
Yes (50 A) Default
setting: switches
off when in
inverter mode
Technical Specifications

Advertisement

Table of Contents
loading

Table of Contents