Technical Specifications - Victron energy MultiPlus-II 48/5000/70-50 230V GX Manual

Inverter/charger off-grid
Table of Contents

Advertisement

8. Technical specifications

MultiPlus-II
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
INVERTER
DC Input voltage range
AC Output voltage
AC output frequency
AC output current
Cont. output power at 25°C (3)
Cont. output power at 25°C
Cont. output power at 40°C
Cont. output power at 65°C
Max apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
CHARGER
AC Input voltage range GENERAL
AC Input frequency range
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Max. battery charge current (4)
Battery temperature sensor
Compatible battery chemistries
GENERAL
Auxiliary AC output
External AC current sensor (optional)
Programmable relay (6)
Protection (2)
Inbuilt GX device
VE.Bus communication port
VE.Can port
VE.Direct port
USB port
Ethernet port
General purpose communication port
Remote on/off terminal
Operating temperature range
Page 17
MultiPlus-II inverter/charger off-grid Australia
48/3000/35-32 230V GX
32A
32A
11A
3000 VA
2400 W
2200 W
1700 W
3000 VA
5500 W
95%
11 W
7 W
2 W
35 A
Lead-acid, Lithium, Zinc-Bromine and others (5)
50A
-20 to +65°C (fan assisted cooling)
48/5000/70-50 230V GX
Yes
50A
50A
38 – 66 V
230 V ± 2%
50 Hz ± 0,1% (1)
19A
5000 VA
4000 W
3700 W
3000 W
5000 VA
9000 W
96%
18 W
12 W
2 W
187-265 V
45 – 65 Hz
5.6 V
55.2 V
52.8 V
70 A
Yes
Yes (32A)
100A
Yes
a - g
Yes
Yes
Yes
Yes
Yes
Yes
Yes, 2x
Yes
Technical specifications

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multiplus-ii 48/3000/35-32 230v gx

Table of Contents