8. TECHNICAL SPECIFICATIONS

Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C (VA)
Cont. output power at 25°C (W)
Cont. output power at 40°C (W)
Cont. output power at 65°C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero-load power in AES mode (W)
Zero-load power in Search mode (W)
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary AC output
Programmable relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
120 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 50Hz
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 120VAC on inverter output
g. Input voltage ripple too high
Input voltage range: 95-130 VAC
Output voltage: 120 VAC ± 2%
(3)
(4)
Operating temp.: -40 to +65°C (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
48/3000/35-50/50 120V
Yes
Yes
Input frequency: 45 – 65 Hz
AC-in-1: 50A
AC-in-2: 50A
AC-in-1: 5,3A
AC-in-2: 5,3A
38 – 66
3000
2400
2000
1700
6000
95
25
20
12
57,6
55,2
52,8
35
4
yes
Max load: 25A Switches off when in inverter mode
Yes
a - g
Four M8 bolts (2 plus and 2 minus connections)
Screw terminals 13mm² (6 AWG)
19
362 x 258 x 218
EN 60335-1, EN 60335-2-29
EN 55014-1, EN 55014-2, EN 61000-3-3
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 120V/4A
DC rating: 4A up to 35VDC and 1A upto 60VDC
Power factor: 1
Frequency: 60 Hz ± 0,1%
Humidity (non condensing): max 95%
Protection: IP 21