Fa23 : 0X2A23 (Communication Command 2) - Toshiba TOSVERT VF-AS3 Manual

Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

fa23 : 0x2A23 (Communication command 2)

7.1.2.
VF-MB1/S15
bit
Function
0
(Reserved)
Electric power quantity
1
reset
2
(Reserved)
3
(Reserved)
4
(Reserved)
5
(Reserved)
6
(Reserved)
Maximum deceleration
7
forced stop
Acceleration/decele-
8
ration selection 1
Acceleration/decele-
9
ration selection 2
10
(Reserved)
11
(Reserved)
12
OC stall level switch
13
(Reserved)
14
(Reserved)
15
(Reserved)
Note: Set 0 to reserved bit.
Acceleration time 1 (acc) and deceleration time 1 (dec) are worked when cmod isn't "Communica
(*1):
tion option". If cmod is "Communication option", Acceleration and deceleration time 1 are worked by c
860, c862, c863, c865. See "7.1.
In this case, set 0(Linear) to acceleration/deceleration 1 pattern (f502: 0x2502).(S-pattern is
n't supported.) If S-pattern is needed, use acceleration/deceleration 2 or 3.
0
-
OFF
-
-
-
-
-
Normal
Enabled
00: Acceleration/deceleration 1
01: Acceleration/deceleration 2
10: Acceleration/deceleration 3
-
-
OC stall 1
OC stall 2
-
-
-
TOSHIBA Drive profile
- 30 -
1
-
Electric power quantity (fe76,
Reset
fe77) reset
-
-
-
-
-
Select acceleration/deceleration
1-3 by combination of two bits.
AD1: acc, dec *1
AD2: f500, f501
AD3: f510, f511
-
-
OC stall 1: f601
OC stall 2: f185
-
-
-
" for the detailed information.
E6581818⑭
Note
-
-
-
-
-
-
-
-
-
-
-
-