2. Transportation and Handling

(1) When transporting the outdoor unit, observe the following item. Please transport the unit to the installation
location under packed condition.
●Hanging Method with Packing:
Hang the unit with two ropes
(2)
The following are accessory parts of the outdoor unit. Please confirm it before installation
Connecting Pipe Set
Special Washer
Drain Connector
Noise Filter (RAM-200, 250FSPH)
(3) Before Installation
●The pressure of refrigerant R410A is 1.4 times higher than conventional refrigerant; it is contaminated easily
by moisture, oxide, oil and other impurities. New refrigerant is adopted; therefore refrigerant oil also need to
be changed. When Installing, make sure to prevent moisture, oxide, oil, refrigerant oil, or other impurities
form getting into the refrigerant cycle.
●Measuring instrument or tool which is directly contact to refrigerant must be used only for refrigerant R410A.
[Legend:○for new and old type refrigerant
for two type R410A and R407C]
Measuring
Instrument and Tools
Pipe Cutter
Flaring Tool
Gasket for pipe
expansion
Pipe Bender
Expanding Tool
Torque Wrench
Brazing Tool
Nitrogen Gas
Lubrication Oil
(for flare
surface)
Refrigerant
Cylinder
Vacuum Pump
Rectifier for
Vacuum Pump
(prevent from
reverse)
.
Description
Interchangeability
Reason of non-interchangeability and precautions
with R22
R407C R410A
To ensure the high pressure of R410A, if using flaring tube,
○■
make the dimension of tube larger for R410A. If you continue
to use existing product, shall be used with flaring tube
(Not
adjustment gasket (1mm). (R410A special flaring tool can be
use)
used directly in the R407c)
R410A for Φ12.7, Φ15.88; spanner size is up 2mm; existing
product cannot be used
For Φ6.35、Φ9.53、Φ19.05; spanner size is the same.
Perform correct brazing work.
Strict control against contamination. (Blow nitrogen during
brazing)
Use a synthetic oil (FVC68D) which is equivalent to the oil
used in refrigerant cycle.
Do not use R22 with mineral oil, and products must be used
the same synthetic oil.
Synthetic oil absorbs moisture quickly. Do not place it in the
humid environment.
Check refrigerant cylinder color.
(R410A:pink), (R407C:brown)
◎Refrigerant must be charge in a state of liquid. (Charging
in a state of gas is strictly prohibited.)
◎The current ones are applicable. However, it is required to
mount a vacuum pump adapter which can prevent from
※●
reverse flow when a vacuum pump stops.
●Hanging Method without Packing:
Hang the unit with two ropes.
Q'ty
Place of use
1
Used to connect gas piping
4
Fixing of Unit Base
1
Base drainage for water
1
Power Ground Wire
only for R410A (not for R22)
(only for new refrigerant)
(◎ Strictly Required)
3
Thickness of
plywood or
cardboard must
be 15mm above.
.
Instruction
Please refer to page 8
Please refer to page 6
Please refer to page 6
Please refer to page 15
●only for R407C (not for R22)
Purpose
Cutting and
deburring pipe
Flaring for tubes
Dimensional control
for extrusion portion
of tube after flaring
Bending
Expanding Tubes
Connection of
Flare Nut
Brazing for Tubes
Prevention from
oxidation during
brazing
Applying oil to
the flared
surface
Refrigerant
Charging
Vacuum
Pumping