Hitachi RAM-20MQ Installation & Maintenance Manual
Hitachi RAM-20MQ Installation & Maintenance Manual

Hitachi RAM-20MQ Installation & Maintenance Manual

Inverter-driven multi-split system air conditioners

Advertisement

Quick Links

Installation&Maintenance Manual
Models:
8HP
10HP
RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D) RAM-20MQ(D) RAM-22MQ(D) RAM-24MQ(D)
◼ Be sure to hand over this manual to constructor of next step and finally let the customer keep it.
(Transportation and Handling) → (Refrigerant Piping) → (Electrical Wiring) → (Test Run) → (Customer)
Important Notice
⚫ This air conditioner has been designed for common air conditioning for people. Do not apply to other purposes such as for food, animals,
plants, high precision machines or work of art.
⚫ Do not install the unit in the following places. It may cause fire, deformation, corrosion or failure.
○ Places where is filled with mineral oil mist or oil spray (including machinery oil) or vapor is produced.
○ Places where is filled with sulfurous gas such as hot spring area.
⚫ Do not install the unit in the following places, it may cause corrosion.
○ Places where strong salty wind blows such as coast regions.
○ An acid or alkaline environment.
⚫ Pay attention to the following situations when the unit is installed in a hospital or other facilities where electromagnetic wave is radiated from
medical equipment.
○ Do not install the unit where the electromagnetic wave is directly radiated to the electrical box, remote control cable or remote control
switch.
○ To avoid the influence of electromagnetic waves via air, wave generating machines such as radio, medical equipment must be kept at
least 3 meters from air conditioner.
⚫ Do not install the unit in the place where wind directly blows on animals or plants. It could adversely affect the animals or plants.
⚫ Using wireless remote controller, the receiver may fail to receive signals due to effect of the lighting equipment. Therefore keep the receiver
away from the lighting equipment more than 1 meter as possible.
Safety Summary
⚫ Before installation, read this section carefully in order to install correctly.
⚫ This manual contains "
serious injury. Therefore, make sure to observe important messages of safety.
⚫ While checking any abnormality during the test run after installation, explain to customer the correct methods of usage and maintenance
according to the instructions of user's manual. Then hand over the installation manual and user's manual to customers.
【 Meaning of symbols】
DANGER:Indicates a hazardous situation which, If not avoided,
may result in death or serious injury.
:Mandatory Symbol: indicate instructing behavior of
general users.
About Electrical Works
⚫ Assign an authorized dealer to perform the electrical work. Please note that if improperly performed by yourself, it may result in
electric shock.
⚫ Perform electrical work according to relevant national regulations and the installation manual. Make sure to use the exclusive
circuit to avoid electric shock or fire due to insufficient capacity of power or improper work.
⚫ Use only specified wires for wirings between units. Incorrect selection of wires also causes fire or electric shock.
⚫ Properly fasten the terminals of wirings. Improper fastening the joint of terminals may result in fire, electric shock or the
overheated terminals.
⚫ Fix the cables securely. External forces on the terminals could lead to a fire.
DANGER
⚫ Installation of an earth leakage breaker (ELB) is necessary. If an ELB is not installed, current leakage may occur.
⚫ When opening the service cover due to need of wiring work or inspection, make sure to completely cut off power before work
to avoid electric shock.
⚫ Perform grounding according to the grounding work instructions. Incident of electric shock may occur if indoor and outdoor units
are not grounded. The ground wire must not be connected to gas pipe, water pipe, lighting rod and ground wire of telephone line.
If the ground wire is not properly connected, it may result in electric shock.
About installation
⚫ Installation must be done in accordance with this installation manual. Improper installation may result in water leakage, electric
shock or fire.
⚫ Install the air conditioner on a foundation strong enough that it can withstand the weight of the unit. A foundation of insufficient
strength may result in the unit falling and injury.
⚫ Do not perform installation at locations subject to existence or entry of flammable gas.
DANGER
⚫ Do not climb or put any object on the air conditioner to prevent injury caused by the unit falling.
⚫ In the event of refrigerant leakage, immediately turn off the fire source (e.g. stoves), wipe the refrigerant off the floor, open the
door and windows for ventilation and then contact the service personnel or the dealer.
INVERTER-DRIVEN
MULTI-SPLIT SYSTEM
AIR CONDITIONERS
Outdoor Units
12HP
14HP
Danger" symbol. This symbol indicates a hazardous situation which, if installed incorrectly, it may result in death or
16HP
18HP
:Mandatory Symbol: indicate grounding must be performed for
machine with grounding terminal.
:Indicate prohibited item.
1
20HP
22HP
24HP
66MP1565

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi RAM-20MQ

  • Page 1 22HP 24HP RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D) RAM-20MQ(D) RAM-22MQ(D) RAM-24MQ(D) ◼ Be sure to hand over this manual to constructor of next step and finally let the customer keep it. (Transportation and Handling) → (Refrigerant Piping) → (Electrical Wiring) → (Test Run) → (Customer) Important Notice ⚫...
  • Page 2: Common Items

    (1) Confirmation of unit model 1) Base unit Model RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D) RAM-20MQ(D) RAM-22MQ(D) RAM-24MQ(D) (2) Combination of Indoor Unit and Outdoor Unit Please refer to the table, select outdoor unit and indoor unit number and capacity.
  • Page 3: Transportation And Handling

    2. Transportation and Handling (1) Operation temperature range Condition Air Inlet Temperature of Outdoor Unit Air Inlet Temperature of Indoor Unit (Non-room Temperature) Item -5℃ DB ~ 43℃ DB 21℃ DB/15℃ WB ~ 32℃ DB/23℃ WB Cooling DB:Dry Bulb WB:Wet Bulb (2) When transporting the outdoor unit, observe the following items.
  • Page 4: Before Installation

    3. Before Installation (1) The pressure of refrigerant R410A is 1.4 times higher than conventional refrigerant; it is contaminated easily by moisture, oxide, oil and other impurities. New refrigerant is adopted; therefore refrigerant oil also needs to be changed. When installing, make sure to prevent moisture, oxide, oil, conventional refrigerant or refrigerant oil, or other impurities from getting into the refrigerant cycle.
  • Page 5 different refrigerant >; If used, mineral oil will ● □ Charging Hose flow into the cycle and cause sludge, resulting in clogging or compressor failure. ‧Please use the weight scale. Charging Cylinder Prohibited Refrigerant Charging Measuring Instrument for ○ ○ Weight Scale Refrigerant Charging ‧The current gas leakage detector(R22) is not...
  • Page 6: Installation Work

    4. Installation Work (1) Selection of Installation Location 1) Make sure the space for operation and maintenance service is secured around the outdoor unit. 2) Install the outdoor unit where it is dry and well ventilated. 3) Install the outdoor unit where it is in the shade or it will not be exposed to direct sunshine or direct radiation from high temperature heat source.
  • Page 7: Multiple Unit Installation

    Unit:mm <Multiple Unit Installation> Min. 25 Min. 25 3.Walls in 4 Directions <Single Unit Installation> <Multiple Unit Installation> ● Keep the upper side open. ● The front side should be less than 1,500mm; air inlet side should be less than 500mm; other sides are no limits. ●...
  • Page 8 (3) Foundation Work Please perform this work properly. Ensure the unit does not lean, vibrate, make a noise or fall in the event of strong wind or earthquake. 1) The height of the base should be 150 mm higher than the ground level. 2) Perform adequate drainage around the foundation.
  • Page 9 (4-38x15 round-end hole) RAM-18MQ(D) Anti-vibration rubber pad 防震橡膠墊(前後共6處) (6-Places) 現地準備 After the Ground 80 above 80以上 120 above 120以上 RAM-20MQ(D) RAM-22MQ(D) M12 Foundation bolt hole RAM-24MQ(D) M12 基礎螺栓孔(4-38x15 長圓孔 (4-38x15 round-end hole) M12膨脹螺栓孔(6-38x15長圓孔) Anti-vibration rubber pad (6-Places) 防震橡膠墊(前後共6處) After the Ground...
  • Page 10 Spare Wiring Hole ( Circuit Connection 操作回路配線孔(Ø33) ø Wiring hole ( ø 排水孔(Ø26 x 2) Drain Hole ( 26 x 2) 排水接頭安裝位置 RAM-20MQ(D) Drain Connector Position RAM-22MQ(D) RAM-24MQ(D) Refrigerant Piping 此孔未使用 冷媒配管接續孔 This Hole is not used Connection Hole (□80 x 127)
  • Page 11: Refrigerant Piping

    2) Drain connector installation methods: 1.Set the washer on the upper part of drain connector. 2.According to the shape of base drain holes, insert the drain connector and turn it clockwise about 40°. 3.Drain connector is equivalent to VP20. 4.Drain pipe is field supplied. Note:The drain connector is installed for discharging condensation water Base Drain...
  • Page 12 ● Piping Size and Multi-Kit Selection Slave (C) Master (A) Slave (B) Example of System : The figure is an example which shows the combination of indoor and outdoor units. Piping Piping 分歧管 1 分歧管 2 Connection Kit 1 The refrigerant pipes which contain gas/ liquid Connection Kit 2 First 第一分歧管...
  • Page 13 5.0~5.6 15.88 / 6.35※ 6.3~16.0 15.88 / 9.53 ※:When piping length exceeds 15m, liquid piping diameter must change to Φ9.53. ●Piping diameter restriction on indoor units: RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D) RAM-20MQ(D) RAM-22MQ(D) RAM-24MQ(D) Model 22.2 25.4 28.6 31.75 Piping a≧100m...
  • Page 14 (Indoor Unit on Left Side) (Indoor Unit on Right Side) Master (A) 18MQ(D) 18MQ(D) 18MQ(D) 24MQ(D) 22MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) Combination 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 24MQ(D) 22MQ(D) 24MQ(D) 22MQ(D) 24MQ(D) 24MQ(D) Unit (B) Model 14MQ(D) 16MQ(D) 18MQ(D) 14MQ(D) 18MQ(D) 18MQ(D) 14MQ(D) 18MQ(D) 18MQ(D) 22MQ(D) 22MQ(D) 24MQ(D) Unit (C) Piping Connection Kit...
  • Page 15 Master (A) 24MQ(D) 22MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) Unit (B) Combination Model 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 24MQ(D) 24MQ(D) 24MQ(D) 22MQ(D) 24MQ(D) 24MQ(D) Unit (C) 14MQ(D) 18MQ(D) 18MQ(D) 14MQ(D) 16MQ(D) 18MQ(D) 14MQ(D) 16MQ(D) 18MQ(D) 22MQ(D) 22MQ(D) 24MQ(D) Unit (D)
  • Page 16 E-NP692S E-NP902S Type Piping Q’ty Liquid Piping Q’ty (2) Caution about Outdoor Unit Installation 1.Align the outdoor units and locate large capacity Master (A) on the indoor unit side. Piping length between Piping Connection Kit 1 and each outdoor unit should be less than 10m. HP:Master (A) ≧...
  • Page 17: Outdoor Unit

    回油彎折高度 回油彎折高度 回油彎折高度 連接至室內機 連接至室內機 200mm以上 200mm以上 200mm以上 回油彎折高度 回油彎折高度 回油彎折高度 連接至室內機 200mm以上 200mm以上 200mm以上 3.Piping length between piping connection kit (at outdoor unit side) and outdoor unit should be less than 2m. In case that the piping length between outdoor units exceeds 2m, an oil trap (min.200mm) should be provided for the gas pipe so that accumulation of refrigerant oil may not occur.
  • Page 18 Unit: mm Model Liquid Line Gas Line RAM-8MQ(D) Ø19.05 Ø9.53 RAM-10MQ(D) Ø22.2 Ø9.53 Ø22.2 Ø9.53 RAM-12MQ(D) Ø25.4 Ø12.7 Ø12.7 RAM-14MQ(D) Ø25.4 Ø12.7 RAM-16MQ(D) Ø28.6 Ø25.4 Ø12.7 Ø15.88 RAM-18MQ(D) Ø28.6 RAM-20MQ(D) Ø28.6 Ø15.88 RAM-22MQ(D) Ø28.6 Ø15.88 Ø28.6 Ø15.88 RAM-24MQ(D) Ø28.6 Ø15.88...
  • Page 19 (4) Setting of the multi-kit pipe ● It is necessary to use optional multi-kit to prevent unit’s insufficient capacity due to the uneven distribution of the refrigerant. Do not use connectors to connect. 1) The installation of the main branch as shown below ‧...
  • Page 20 2) Fixed the multi-kit piping 1.Horizontal ‧The branch pipe must be set in the same plane. ‧Keep the outdoor unit pipes straight at least 0.5m after piping connection kits. Straight Pipe 0.5m Above In the same Horizon Plane Down Down 2.Vertical ‧Upward Branch:Keep the outdoor unit pipes straight at least 0.5m after piping connection kits.
  • Page 21 (7) Refrigerant Piping Work 1) Confirm that the stop valves of outdoor unit are closed. 2) Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Fix the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched, abnormal sound may occur due to the vibration of the piping, especially short length piping.) 3) Please connect the piping between indoor and outdoor unit.
  • Page 22 W + Wo = 100 kg RAM-8~10MQ(D) RAM-12MQ(D) Note: RAM-14MQ(D) : Factory refrigerant charging weight. RAM-16MQ(D) RAM-18MQ(D) 10.7 Additional Refrigerant RAM-20MQ(D) 11.3 System Refrigerant RAM-22MQ(D) Additional Refrigerant Date RAM-24MQ(D) 11.6 Note: ‧W is outdoor unit ref. charge before shipment. ‧In case of the combination of the base unit, calculate the total ref.
  • Page 23 Outdoor Unit 1) Fully open the gas line stop valve. Nitrogen Bottle (Use for Brazing and 2) After cooling operation starts, connect the gauge manifold Air-Tight Test) Manifold Gauge using charging hoses with a refrigerant charging cylinder Liquid Line Stop Valve to the check joints of the liquid line stop valve to charge refrigerant.
  • Page 24 Poles Current (mA) 60Hz RAM-8MQ 25.5 RAM-10MQ 35.0 RAM-12MQ 39.0 RAM-14MQ 48.0 230V 54.5 RAM-16MQ 61.5 RAM-18MQ 2-Core 72.5 RAM-20MQ Shielded 73.5 RAM-22MQ Twist Pair 87.0 Cable RAM-24MQ 0.75(mm RAM-8MQD 15.5 Total Length RAM-10MQD 21.5 Below 24.0 RAM-12MQD 1000m 29.5...
  • Page 25 (2) Wiring Instruction ●The power source cord and transmission cable wiring, please follow the following instruction to implement. 1) The outdoor unit's power source cord must be wired separately, and each outdoor unit must have individual high-speed type earth leakage breaker (ELB) and the power switch. 2) Connect the power supply wiring to each indoor unit group which is connected to the same outdoor unit.
  • Page 26 6) Check the capacity of the electrical wires. If the power source capacity is too low, the system cannot be started due to the voltage drop. 7) If the indoor and outdoor unit is not grounded it may cause electric shock and other accidents, be sure to implement grounding.
  • Page 27 11) Wire connection port: When the power supply is 380V, connect the power supply to TB1 of L1, L2, L3 and N; When the power supply is 230V, connect the power supply to TB1 of R, S, T, and the earth wire should be fastened on the power supply box.
  • Page 28 7. Dip Switch (DSW) Setting of Outdoor Unit TURN OFF all power sources before setting. Without turning OFF, the switches do not work and the contents of the setting are invalid. ( The mark of ■ indicates the position of dip switches.) Enter...
  • Page 29 (1) Implementation the H-LINKII connection, need to setting refrigerant cycle number (only outdoor unit(master)) and end terminal resistance.(outdoor unit(slave) no need setting) ● Setting of refrigerant cycle number The same refrigerant system outdoor unit and indoor unit must be set to the same refrigerant system number for the outdoor unit and the indoor unit as shown below.
  • Page 30 8. Test Run 【Before Test Run】 ● Before test run, please re-confirm the installation whether there are problems, also confirm the following points. ● In addition, please confirm it with the installation manual attached to the outdoor unit. 1) Refrigerant piping and the transmission cable if connected with a different refrigerant cycle, abnormalities will occur. 2) Please use the 500V electrical resistance tester to confirm the electrical parts between terminals and earth electrical resistance must be more than 1MΩ.
  • Page 31: Alarm Code

    Alarm Code Code Category Content of Abnormality Leading Cause Activation of float switch (High water level in drain pan, abnormality of drain Indoor Unit Activation of protection device (Float switch) pipe, float switch or drain pan) Activation of protection device Outdoor Unit Activation of PSH (Pipe clogging, excessive refrigerant, inert gas mixing) (High pressure cut)
  • Page 32 This alarm code appears when the following alarm* occurs three times within Compressor protection alarm Compressor 6 hours. (It can not be reset from remote controller.) *02, 07, 08, 39, 43 to 45, 47 Outdoor Unit Incorrect outdoor unit address number or unit The number set for address or refrigerant cycle is over 64.
  • Page 33 Test Run and Maintenance Record MODEL: SERIAL. No. COMPRESSOR MFG. No. DATE: CUSTOMER'S NAME AND ADDRESS: 1. Is the rotation direction of the indoor coil fan correct? YES/NO 2. Is the rotation direction of the outdoor coil fan correct? YES/NO 3.
  • Page 34 MEMO...
  • Page 35 MEMO...
  • Page 36 66MP1565-A1 Printed in Philippines...