Data
Power supply U
Max. current consumption
Max. load R
Impact of power supply
Load influence
Temperature impact
Ambient temperature
1)
Power supply possible via: AC, AM actuator controls or external power supply
2)
Depending on temperature range of the actuator: refer to name plate
Setting elements The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to
All settings are made via the two push buttons [S1] and [S2].
Figure 43: View on control unit when switch compartment is open
[S1]
LED
[1]
[S1]
LED
[2]
The output current (measuring range 0 – 20 mA) can be checked at measuring points
[1] and [2].
Table 19: Short overview on push button functions
Push but-
tons
[S1] + [S2]
[S1]
[S2]

11.3.1 Set measuring range

For setting, voltage must be applied at the electronic position transmitter.
For output current verification, connect a test device for 0 – 20 mA to measurement
points (+/–) (for 2-wire systems, connecting a test device is imperatively required).
1)
V
B
2)
Push button: Set 0/4 mA
Optical aid for setting
Measuring point (–) 0/4 – 20 mA
Function
→ press simultaneously for 5 s: Activate setting mode
→ press in setting mode for 3 s: Set 4 mA
→ press in setting mode for 6 s: Set 0 mA (only possible for 3-/4-wire version)
→ press in operation for 3 s: Switch on/off LED end position signalling
→ touch in end position: Reduce current value by 0.02 mA
→ press in setting mode for 3 s: Set 20 mA
→ press in operation for 3 s: Switch on/off LED end position signalling
→ touch in end position: Increase current value by 0.02 mA
Commissioning (optional equipment settings)
3-wire and 4-wire systems
24 V DC (18 – 32 V)
LED off = 26 mA,
LED on = 27 mA
600 Ω
< 0.1 ‰/K
–60 °C to +80 °C
Open switch compartment
[S2]
Push button: Set 20 mA
[1]
Measuring point (+) 0/4 – 20 mA
2-wire system
24 V DC (18 – 32 V)
20 mA
(U
– 12 V)/20 mA
V
0.1 %
0.1 %
[} 33].
[S2]
[2]
41