16
Figure 12: Fit actuator
ð Information: Ensure that the spigot (if provided) fits uniformly in the recess
and that the flanges are in complete contact.
7. If flange bores do not match thread: Slightly rotate handwheel until bores line up.
8. If the bores do not align even after rotating the handwheel, shift the actuator by
one tooth on the coupling, if required.
9. Fasten actuator with screws.
10. Tighten screws crosswise with a torque according to the table in chapter
ing torques for screws
[} 54].
Tighten-