Commissioning
The tests must first be enabled and then activated.
N
The pump tests (brine pump and circulation pump) can be carried out
N
in any order.
The test cases in the table below are available in MANUAL TEST.
Additional test cases may be applicable if external applications are in-
N
stalled and activated.
Parameter
Meaning
Compressor
0 = compressor stopped
Set compressor gear 1 –9
0 = stop brine pump
Brine pump
1 = start brine pump
0 = stop circulation pump
Circulation pump
1 = start circulation pump
Three steps: 1, 2 and 3.
Internal Immersion
heater
0 % = heat
HGW
100 % = tap water
Danfoss Heating Solutions
DHP-H Varius Pro+/DHP-L Varius Pro+
VIJSG202
23