SMA SUNNY BOY 3.8-US User Manual page 41

Hide thumbs Also See for SUNNY BOY 3.8-US:
Table of Contents

Advertisement

SMA Solar Technology America LLC
Event number
8206
8503
8708
8801 to 8803
9002
9003
User Manual
Message, cause and corrective measures
Electr. arc detected > Please confirm by tapping
The inverter has detected an electric arc and was recommissioned after a dis-
connection. By tapping, you are confirming that you have repaired any possi-
ble damage to PV modules, DC conductors or plugs in the PV system.
Corrective measures:
• Tap on the enclosure lid of the Connection Unit within ten seconds of the
message appearing in order to recommission the inverter.
Self-diagnosis > Input C defective
The cause must be determined by the Service.
Corrective measures:
• Contact the Service (see Section 11 "Contact", page 67).
Timeout in communication for active power limitation
Communication to the system control absent. Depending on the fall-back set-
ting, either the last received values will be retained or the active power will be
limited to the set percentage value of the inverter nominal power.
Corrective measures:
• Ensure that the connection to the system manager (e.g.
Sunny Home Manager) is intact and that no cables are damaged or that
no plugs have been pulled.
No display
No information can be shown on the display.
SMA Grid Guard code invalid
The SMA Grid Guard code entered is incorrect. The operating parameters are
still protected and cannot be changed.
Corrective measures:
• Enter the correct SMA Grid Guard code.
Grid parameter locked
Changes to the grid parameters are now blocked. In order to be able to make
changes to the grid parameters, from now on you must log in using the SMA
Grid Guard code.
SB30-77-1SP-US-40-BA-en-11
8 Troubleshooting
47