Using Front-Connected Pc - Hitachi Relion RES670 Commissioning Manual

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

1MRK 511 409-UUS Rev. K
13.2.2

Using front-connected PC

When an internal fault has occurred, extensive information about the fault can be retrieved from the list of
internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during commissioning and
fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list. The list can store up to
40 events. The list is based on the FIFO principle, when it is full, the oldest event is overwritten. The list
cannot be cleared and its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities, such as
change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC can be
connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 19:
Event message:
INT--FAIL
INT--FAIL
INT--WARNING
INT--WARNING
IOn--Error
IOn--Error
ADMn-Error
ADMn-Error
MIM1-Error
MIM1-Error
INT--RTC
INT--RTC
INT--TSYNC
INT--TSYNC
INT--SETCHGD
DRPC-CLEARED
The events in the internal event list are time tagged with a resolution of 1ms.
Phasor measurement unit RES670
Commissioning manual
IED will not be operational during applications restart.
Events available for the internal event list in the IED
Description
Off
Internal fail status
Off
Internal warning status
Off
In/Out module No. n status
Off
Analog/Digital module No. n
status
Off
mA-input module status
Off
Real Time Clock (RTC) status
Off
External time synchronization
status
Any settings in IED changed
All disturbances in Disturbance
report cleared
© 2017 - 2022 Hitachi Energy. All rights reserved
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
INT--TSYNC (reset event)
INT--TSYNC (set event)
Section 13
Troubleshooting
M11763-203 v6
163