Current Protection; Directional Phase Overcurrent Protection, Four Steps Oc4Ptoc (51_67) - Hitachi Relion RES670 Commissioning Manual

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
2
1
0
1
0
-1
2
1
0
2
1
0
2
1
0
1
0
-1
0
IEC10000142 V1 EN-US
Figure 26:
11.4

Current protection

11.4.1
Directional phase overcurrent protection, four steps OC4PTOC
(51_67)
Prepare the IED for verification of settings outlined in Section
Values of the logical signals for OC4PTOC are available on the local HMI under Main menu/Tests/
Function status/Current protection/PhaseOverCurrent4Step(51_67,4(3I>)) /
OC4PTOC(51_67;4(3I>)):x, where x = instance number.
The Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
106
COMMON TRIP COMMAND (trip)
TRIPZ1 (tripZone1)
TRIPZ2 (tripZone2)
GENMODE (generatorMode)
MOTMODE (motorMode)
0.5
1
1.5
2
time in seconds
Boolean output signals for the injected current with two components: a 50 Hz current
component and a 49.5 Hz current component
© 2017 - 2022 Hitachi Energy. All rights reserved
START (start)
2.5
3
3.5
"Preparing the IED to verify
1MRK 511 409-UUS Rev. K
4
4.5
5
IEC10000142-1-en.vsd
settings".
Phasor measurement unit RES670
Commissioning manual
SEMOD53531-1 v1
SEMOD56287-67 v9