Section 4: Module Setup and Calibration
July 2019
4.5.2

Calibrate Analog Output (Position Feedback)

1.
2.
3.
4.
5.
6.
7.
4.5.3

Select Modulation Delay Time

1.
2.
3.
4.
15
Connect calibrated 4-20mA meter to TBM Terminals 50 (-) and 51 (+).
Set S2 to ON (up) position.
Press UP or DOWN push button to increase or decrease zero (4mA) analog
output signal.
Return S2 to OFF (down) position.
Set S3 to ON (up) position.
Press UP or DOWN push button to increase or decrease full-scale (20mA) analog signal.
Return S3 to OFF (down) position.
Set S1 and S2 to ON (up) position.
Press UP push button to select 3-Phase motor (Modulation delay = 2 seconds).
Press DOWN push button to select 1-Phase motor
(Modulation delay = 12 seconds).
Return S1 and S2 to OFF (down) position.
Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
Module Setup and Calibration