Pulsing Control (S1, S2, S3, S4, S6 On & S5 Off) - Emerson Bettis 2000 Series User Manual

Hide thumbs Also See for Bettis 2000 Series:
Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
MAN-02-04-55-0735-EN Rev. 0
4.3.10
Pulsing Control (S1, S2, S3, S4, S6 ON & S5 OFF)
Press UP to Select Pulsing Control - Figure 13.
Press DOWN to Disable Pulsing Control to default values - Figure 13.
Figure 13
NOTE
New for firmware Ver 4.6, default setting for Pulsing Control is OFF/Disabled.
ON/Enabled Pulsing Control not recommended for Digital Futronic II, III and VII for any
operating condition, or Futronic IV when either the input command signal is constantly
changing, or stroke time is greater than one (1) minute. ON/Enabled Pulsing Control
directs actuator to continue operation (motor power cycles on and off) within the control
bandwidth of setpoint.
Module Setup and Calibration
Section 4: Module Setup and Calibration
July 2019
12