Section 4: Module Setup and Calibration
July 2019
4.5.6

Assign Digital Futronic Type (New for Ver 4.6)

Firmware Ver 4.6 requires the Digital Futronic type to be actively configured. Previous
firmware Ver 4.2 and below only require setting the DIP Switches S5 and S6.
1.
2.
3.
4.
5.
4.5.7

Calibrate To Limits (New for Ver 4.6)

Firmware Ver 4.6 requires the Digital Futronic actuator position limits to be configured and
verified by using a push button.
6.
7.
8.
Analog Position Feedback Fully Open (LSO Active)
1.
2.
Analog Position Feedback Fully Close (LSC Active)
1.
2.
17
Set DIP Switches S5 and S6 (See Table 1) to assign Digital Futronic type.
Set S1 and S4 to ON (up) position.
Set S2 and S3 to OFF (down) position.
Selector Switch in OFF
Press UP push button to accept the actuator type configuration.
Digital Futronic Type
DF III
DF IV
DF VII
Set S1, S2, S3, and S4 to OFF (down) position.
Place selector switch in Local.
Stroke Valve to fully open and fully close at least once.
Stroke Valve a second time to Fully Open
Press UP Push Button until LED1 display pattern flash rate changes
Stroke Valve to Fully Close a second time
Press DOWN Push Button until LED1 display pattern flash rate changes
Installation, Operation and Maintenance Manual
DIP Switch Position
5 ON, 6 OFF
5 OFF, 6 ON
5 ON, 6 ON
MAN-02-04-55-0735-EN Rev. 0
Reference Section 4.4 (Figure)
Fig 16
Fig 17
Fig 18
Module Setup and Calibration