Multiport Flow Selector
January 2019
Valve Status Monitor
The Status Monitor is a valuable tool for monitoring
and commissioning the system. It provides a
Dashboard for quick visual indication of status and
provides tab for review of Alarm and ESD Status, as
well as Device Info. This screen may be used to
determine command and position status troubleshoot
any problems should they occur. Red Tabs indicate an
active alarm or event exists. Field diagnostic code or
Alarms are displayed in the Monitor Tab. All active
alarms may be viewed at a glance in the Alarms tab.
See figures 21 through 23.
Mode displays the mode selected by the selector
switch of the LDM or combined logic of both LDM and
RDM selector switches.
Monitor provides a snapshot of the active conditions
and and Logs displays the last 9 Alarms.
At Port displays the port number position of the
actuator and whether the MPA is at the port within 1
degree or within 2 degrees.
Torque is displayed as percentage of the full torque
rating of the actuator. Torque is displayed from 10% to
99% in 1% increments. Torque less than 10% is
displayed as zero because torque between 0% and 10%
cannot be accurately measured.
Tracking and trend graphics display Setpoint, Position,
and Torque over travel time.
Encoder Value is the 12-bit raw data from the position
encoder in the range of 0 to 4095. This value is the
same as the value displayed during Port Calibration in
the Factory on the Factory Setup screen so it can be
compared to port calibration value of each port.
38
Figure 21.
Figure 22.
Figure 23.
Instruction Manual
D104239X012
Need help?
Do you have a question about the Fisher Multiport Flow Selector and is the answer not in the manual?
Questions and answers