2.4 Functional Scope
2.4.2

Setting Notes

Peculiarities
Most settings are self-explanatory. The special cases are described below.
If the setting group change function has to be used, address 103 Grp Chge OPTION must be set to enabled.
In this case, it is possible to apply two groups of settings for function parameters (refer also to Section 2.6) al-
lowing convenient and fast switch-over between these setting groups. The setting Disabled implies that only
one function parameter setting group can be applied and used.
Parameter 104 FAULT VALUE is used to specify whether the oscillographic fault recording should record
Instant. values or RMS values. If RMS values is stored, the available recording time increases by the
factor 16.
For some protection functions you can also choose the measuring inputs of the device to which they will be
allocated (side 1 or side 2); for other functions the allocation is fixed (see table 2-1).
For example, address 112 O/C PROT. I> allows such a choice for the I> stage of the time-overcurrent pro-
tection (= Side 1, Side 2 or Disabled).
For the high-current stage I>> of the overcurrent protection, address 113 O/C PROT. I>> determines whether
stage NonDirec. SIDE1 or NonDirec.SIDE 2 or Direc. SIDE1 or Direc. SIDE2 is to be operative.
By selecting Disabled, this overcurrent stage can be excluded altogether. For the inverse time overcurrent
protection 114 O/C PROT. Ip, different sets of dependent characteristics are available, depending on the
version ordered; they are either according to IEC or according to ANSI. This function, too, can be allocated to
either side 1 or side 2 (= IEC SIDE 1, ANSI SIDE 1, IEC SIDE 2, ANSI SIDE 2). Inverse time overcurrent
protection can be excluded altogether by selecting Disabled.
The following table shows the allocation of device inputs to the protection functions. The interdependencies
shown here must be kept in mind when configuring the power system. This concerns the U
sitive current inputs I
e.g. by the stator earth fault protection functions, it is no longer available for rotor earth fault protection (R, fn).
The same interdependencies apply for measured value transformer inputs. They can be used only by one pro-
tection function in each case. Where the TDs are not used by any protection function, they are available for
general processing by the measured value blocks in CFC.
Table 2-1
Allocation of Device Inputs to Protection Functions
Protection function
Definite-time I>; I>> /non-directional
Definite-time I>>/directional
Inverse-time overcurrent protection
Thermal Overload Protection
Unbalanced load protection
Startup Overcurrent Protection
Differential Protection (ANSI
87G/87M/87T)
Earth Fault Differential Protection
Underexcitation (Loss-of-Field) Protec-
tion (ANSI 40)
Reverse Power Protection (ANSI 32R) Fixed
Forward power supervision
Impedance protection
44
and I
as well as the 3 measuring transducer inputs (TD). Where the U
ee1
ee2
U
; U
; U
L1
L2
L3
Fixed
Selectable
Fixed
Selectable
Fixed
Selectable
Selectable
Fixed
U0 (calculat-
Selectable
ed)
Fixed
Fixed
Fixed
Side 1
I
; I
I
;
U
L1S1
L2S1
ee1
I
L3S1
C53000-G1176-C149-7, Release date 03.2010
input, the two sen-
E
input is used
E
Side 2
I
; I
I
;
E
L1S2
L2S2
ee2
I
L3S2
Selectable
Selectable
Selectable
Fixed
Fixed
Selectable
Fixed
Selectable
Fixed
Fixed
Fixed
Fixed
Fixed
SIPROTEC, 7UM62, Manual
TD
TD2
TD3

Advertisement

Table of Contents
loading

Table of Contents