Siemens SIPROTEC 7UM62 Manual page 49

Multifunctional machine protection
Hide thumbs Also See for SIPROTEC 7UM62:
Table of Contents

Advertisement

Addr.
Parameter
144
INV.UNDERVOLT.
145
df/dt Protect.
146
VECTOR JUMP
150
S/E/F PROT.
151
O/C PROT. IEE>
152
SEF 3rd HARM.
153
100% SEF-PROT.
154
O/C PROT IEE-B
155
INTERTURN PROT
160
ROTOR E/F
161
REF 1-3Hz
165
STARTUP MOTOR
166
RESTART INHIBIT
170
BREAKER FAILURE
171
INADVERT. EN.
172
DC PROTECTION
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
Setting Options
Disabled
Enabled
Disabled
2 df/dt stages
4 df/dt stages
Disabled
Enabled
Disabled
non-dir. U0
non-dir. U0&I0
directional
Disabled
with IEE1
with IEE2
Disabled
Enabled
Disabled
Enabled
Disabled
with IEE1
with IEE2
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Side 1
Side 2
Disabled
Enabled
Disabled
Enabled
Default Setting
Enabled
Inverse Undervoltage Protection
Up<
2 df/dt stages
Rate-of-frequency-change protec-
tion
Enabled
Jump of Voltage Vector
non-dir. U0&I0
Stator Earth Fault Protection
with IEE2
Sensitive Earth Current Protection
Enabled
Stator Earth Fault Prot. 3rd Har-
monic
Enabled
100% Stator-Earth-Fault Protec-
tion
with IEE2
Sensitive Earth Current Protection
B
Enabled
Interturn Protection
Enabled
Rotor Earth Fault Protection (R,
fn)
Enabled
Rotor Earth Fault Protection (1-
3Hz)
Enabled
Motor Starting Time Supervision
Enabled
Restart Inhibit for Motors
Side 2
Breaker Failure Protection
Enabled
Inadvertent Energisation
Enabled
DC Voltage/Current Protection
Functions
2.4 Functional Scope
Comments
49

Advertisement

Table of Contents
loading