Siemens SIPROTEC 7UM62 Manual page 584

Multifunctional machine protection
Hide thumbs Also See for SIPROTEC 7UM62:
Table of Contents

Advertisement

Appendix
A.7 Settings
Addr.
Parameter
6002
RE< WARN
6003
RE<< TRIP
6004
T-WARN-RE<
6005
T-TRIP-RE<<
6006
X COUPLING
6007
R SERIES
6008
I RE<
6009
PHI I RE
6101
REF 1-3Hz
6102
RE< WARN
6103
RE<< TRIP
6104
T-WARN-RE<
6105
T-TRIP-RE<<
6106
Qc <
6107A
TEST RESISTOR
6501
STARTUP MOTOR
6502
START. CURRENT
6503
STARTING TIME
6504
LOCK ROTOR TIME
6505
I MOTOR START
6601
RESTART INHIBIT
6602
IStart/IMOTnom
6603
T START MAX
6604
T EQUAL
6606
MAX.WARM STARTS
6607
#COLD-#WARM
6608
Kτ at STOP
6609
Kτ at RUNNING
6610
T MIN. INHIBIT
7001
BREAKER FAILURE
7002
TRIP INTERN
7003
CIRC. BR. I>
7004
TRIP-Timer
584
Function
C
Rotor E/F
3.0 .. 30.0 kΩ
Rotor E/F
1.0 .. 5.0 kΩ
Rotor E/F
0.00 .. 60.00 sec; ∞
Rotor E/F
0.00 .. 60.00 sec; ∞
Rotor E/F
-100 .. 800 Ω
Rotor E/F
0 .. 999 Ω
Rotor E/F
1.0 .. 50.0 mA; 0
Rotor E/F
-15.0 .. 15.0 °
REF 1-3Hz
OFF
ON
Block relay
REF 1-3Hz
5.0 .. 80.0 kΩ
REF 1-3Hz
1.0 .. 10.0 kΩ
REF 1-3Hz
0.00 .. 60.00 sec; ∞
REF 1-3Hz
0.00 .. 60.00 sec; ∞
REF 1-3Hz
0.00 .. 1.00 mAs
REF 1-3Hz
1.0 .. 10.0 kΩ
Start Motor
OFF
ON
Block relay
Start Motor
5A
0.50 .. 80.00 A
1A
0.10 .. 16.00 A
Start Motor
1.0 .. 180.0 sec
Start Motor
0.5 .. 120.0 sec; ∞
Start Motor
5A
3.00 .. 50.00 A
1A
0.60 .. 10.00 A
Restart Motor
OFF
ON
Block relay
Restart Motor
1.5 .. 10.0
Restart Motor
3.0 .. 320.0 sec
Restart Motor
0.0 .. 320.0 min
Restart Motor
1 .. 4
Restart Motor
1 .. 2
Restart Motor
1.0 .. 100.0
Restart Motor
1.0 .. 100.0
Restart Motor
0.2 .. 120.0 min
Breaker Failure
OFF
ON
Block relay
Breaker Failure
OFF
BO12
CFC
Breaker Failure
5A
0.20 .. 10.00 A
1A
0.04 .. 2.00 A
Breaker Failure
0.06 .. 60.00 sec; ∞
Setting Options
Default Setting
10.0 kΩ
2.0 kΩ
10.00 sec
0.50 sec
398 Ω
50 Ω
2.0 mA
0.0 °
OFF
40.0 kΩ
5.0 kΩ
10.00 sec
1.00 sec
0.02 mAs
3.3 kΩ
OFF
15.60 A
3.12 A
8.5 sec
6.0 sec
8.00 A
1.60 A
OFF
4.9
8.5 sec
1.0 min
2
1
5.0
2.0
6.0 min
OFF
OFF
1.00 A
0.20 A
0.25 sec
C53000-G1176-C149-7, Release date 03.2010
Comments
Pickup Value of Warning Stage
Re<
Pickup Value of Tripping Stage
Re<<
Time Delay of Warning Stage
Re<
Time Delay of Tripping Stage
Re<<
Coupling Reactance
Series Resistance (e.g. Meas.
Brushes)
Pickup Value of Failure Detection
Ire<
Correction Angle for Ire
Rotor Earth Fault Protection (1-
3Hz)
Pickup Value of Warning Stage
Re<
Pickup Value of Tripping Stage
Re<<
Time Delay of Warning Stage
Re<
Time Delay of Tripping Stage
Re<<
Pickup Value of open Rotor
Circuit (Qc)
Testing Resistor
Motor Starting Time Supervision
Starting Current of Motor
Starting Time of Motor
Permissible Locked Rotor Time
Current Pickup Value of Motor
Starting
Restart Inhibit for Motors
I Start / I Motor nominal
Maximum Permissible Starting
Time
Temperature Equalization Time
Permissible Number of Warm
Starts
Number of Cold Starts - Warm
Starts
Extension of Time Constant at
Stop
Extension of Time Constant at
Running
Minimum Restart Inhibit Time
Breaker Failure Protection
Start with Internal TRIP
Command
Supervision Current Pickup
TRIP-Timer
SIPROTEC, 7UM62, Manual