Addr.
Parameter
9121A
RTD12 TYPE
9122A
RTD12 LOCATION
9123
RTD12 STAGE 1
9124
RTD12 STAGE 1
9125
RTD12 STAGE 2
9126
RTD12 STAGE 2
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
Setting Options
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
2.46 Temperature Detection by Thermoboxes
Default Setting
Not connected
RTD12: Type
Other
RTD12: Location
100 °C
RTD12: Temperature Stage 1
Pickup
212 °F
RTD12: Temperature Stage 1
Pickup
120 °C
RTD12: Temperature Stage 2
Pickup
248 °F
RTD12: Temperature Stage 2
Pickup
Functions
Comments
323