Siemens SIPROTEC 7UM62 Manual page 577

Multifunctional machine protection
Hide thumbs Also See for SIPROTEC 7UM62:
Table of Contents

Advertisement

Addr.
Parameter
281
BkrClosed I MIN
295
TRANSDUCER 1
296
TRANSDUCER 2
297
TRANSDUCER 3
302
CHANGE
401
WAVEFORMTRIGGER
403
MAX. LENGTH
404
PRE. TRIG. TIME
405
POST REC. TIME
406
BinIn CAPT.TIME
610
FltDisp.LED/LCD
611
Spont. FltDisp.
615
T MIN LED HOLD
640
Start image DD
1108
ACTIVE POWER
1201
O/C I>
1202
I>
1203
T I>
1204
U< SEAL-IN
1205
U<
1206
T-SEAL-IN
1207A
I> DOUT RATIO
1301
O/C I>>
1302
I>>
1303
T I>>
1304
Phase Direction
1305
LINE ANGLE
1401
O/C Ip
1402
Ip
1403
T Ip
1404
TIME DIAL: TD
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
Function
C
P.System Data 1
5A
0.20 .. 5.00 A
1A
0.04 .. 1.00 A
P.System Data 1
10 V
4-20 mA
20 mA
P.System Data 1
10 V
4-20 mA
20 mA
P.System Data 1
with filter
without filter
Change Group
Group A
Group B
Binary Input
Protocol
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Osc. Fault Rec.
0.30 .. 5.00 sec
Osc. Fault Rec.
0.05 .. 4.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.10 .. 5.00 sec; ∞
Device
Target on PU
Target on TRIP
Device
YES
NO
Device
0 .. 60 min
Device
image 1
image 2
image 3
image 4
P.System Data 2
Generator
Motor
O/C Prot. I>
OFF
ON
Block relay
O/C Prot. I>
5A
0.25 .. 100.00 A
1A
0.05 .. 20.00 A
O/C Prot. I>
0.00 .. 60.00 sec; ∞
O/C Prot. I>
ON
OFF
O/C Prot. I>
10.0 .. 125.0 V
O/C Prot. I>
0.10 .. 60.00 sec
O/C Prot. I>
0.90 .. 0.99
O/C Prot. I>>
OFF
ON
Block relay
O/C Prot. I>>
5A
0.25 .. 100.00 A
1A
0.05 .. 20.00 A
O/C Prot. I>>
0.00 .. 60.00 sec; ∞
O/C Prot. I>>
Forward
Reverse
O/C Prot. I>>
-90 .. 90 °
O/C Prot. Ip
OFF
ON
Block relay
O/C Prot. Ip
5A
0.50 .. 20.00 A
1A
0.10 .. 4.00 A
O/C Prot. Ip
0.05 .. 3.20 sec; ∞
O/C Prot. Ip
0.50 .. 15.00 ; ∞
Setting Options
Default Setting
0.20 A
0.04 A
10 V
10 V
with filter
Group A
Save w. Pickup
1.00 sec
0.20 sec
0.10 sec
0.50 sec
Target on PU
NO
5 min
image 1
Generator
OFF
6.75 A
1.35 A
3.00 sec
OFF
80.0 V
4.00 sec
0.95
OFF
21.50 A
4.30 A
0.10 sec
Reverse
60 °
OFF
5.00 A
1.00 A
0.50 sec
5.00
Appendix
A.7 Settings
Comments
Closed Breaker Min. Current
Threshold
Transducer 1
Transducer 2
Transducer 3
Change to Another Setting
Group
Waveform Capture
Max. length of a Waveform
Capture Record
Captured Waveform Prior to
Trigger
Captured Waveform after Event
Capture Time via Binary Input
Fault Display on LED / LCD
Spontaneous display of flt.an-
nunciations
Minimum hold time of lachted
LEDs
Start image Default Display
Measurement of Active Power for
Overcurrent Time Protection I>
I> Pickup
T I> Time Delay
State of Undervoltage Seal-in
Undervoltage Seal-in Pickup
Duration of Undervoltage Seal-in
I> Drop Out Ratio
Overcurrent Time Protection I>>
I>> Pickup
T I>> Time Delay
Phase Direction
Line Angle
Inverse O/C Time Protection Ip
Ip Pickup
T Ip Time Dial
TIME DIAL: TD
577