Event Display Lock

If several zones produce an alarm, trouble or supervisory, the system will
display the first zone that produced an event. To display the other zone(s) in
alarm or trouble, press the [

Fire Drill Test (Code + # + 69)

This test causes Notification Appliance Circuits to be activated for the
purpose of conducting a fire drill or a bell test. This can only be activated by
the installer or a master user from Partition 1 keypads as follows:
1. Enter the corresponding security code and press [#} + 69 (make sure the
burglary portion of the system is disarmed). Keypads will display "FIRE
DRILL ACTIVE" while the test is active.
2. The test may be stopped by entering any security code and pressing OFF.
NOTE: The system continues to monitor all 24-hour zones (fire, panic, etc.),
while this test is active, and will end the test when an alarm condition is
detected. This test should be conducted at periodic intervals as determined
by the local authority having jurisdiction.