Table 22: Critical Alarms
Screen Text
Evaporator Pressure Low
Discharge Pressure High
Vanes Not Closed
Oil Pressure Low
Oil Feed Temperature Low
Oil Feed Temperature High
RLA Low (motor open)
Discharge Temperature High
High Pressure Switch
Motor Temperature High
Surge Detected - Running
Surge Condition
No Starter Transition
Starter Fault
Prelube Cycle Failed
Evaporator Water Flow Loss
Condenser Water Flow Loss
Sensor Fault: Evap LWT
Sensor Fault: Evap Sat Press
Sensor Fault: Cond Sat Press
Sensor Fault: Suction Temp
Sensor Fault: Discharge Temp
Sensor Fault: Oil Feed Temp
Sensor Fault: Oil Sump Temp
Sensor Fault: Oil Feed Pressure Rapid Stop/No Start
Sensor Fault: Oil Vent Pressure
External Input Comp Fault
Starter Current Overload
Starter Current Imbalance
Starter Phase Loss
Starter Phase Order
Starter Over Volt
Starter Under Volt
Ground Fault
Sensor Fault: Leaving Heat
Recovery
External Fault Digital Input
Motor Temperature Trip - NTC
Motor Temperature Trip - DI
IGV Actuator Fault
IGV Position Tracking Error
IOM 1274-3 • CENTRIFUGAL WATER CHILLERS
Action Taken
Low or No Evaporator Water Flow. Low refrigerant level in evaporator. Incorrect setpoint value for
Rapid Stop
leaving water temperature.
Rapid Stop
Low or no condenser water Flow
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Low or no condenser water Flow
Rapid Stop
Rotor and/or stator cooling circuit fault
Rapid Stop
Motor stator cooling solenoid not open, rotor cooling stepper motor not functioning correctly,
motor rotor superheat or gain setpoints incorrect (contact factory)
Rapid Stop
Surge Temperature = the suction temperature minus the leaving chilled water temperature.
Rapid Stop/No Start
Surge condition detected while starting
Rapid Stop/No Start
Rapid Stop
Rapid Stop/No Start
Oil pressure too low to start compressor.
Loss of evaporator flow, evaporator pump off, evaporator head gasket leaking or missing, sensor
Rapid Stop
wiring fault, evaporator flow sensor failure
Loss of condenser flow, condenser pump off, condenser head gasket leaking or missing, sensor
Rapid Stop
wiring fault, condenser flow sensor failure
Rapid Stop
Sensor shorted or open. Chilled water flow switch may be open
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop/No Start
Sensor shorted or open. Check for loose wires or failed sensor
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Rapid Stop
Troubleshooting
60
Operation
Clear
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual