Installation and Maintenance Manual IM 743-7 Group: Controls Part Number: IM 743 Date: June 2022 MicroTech II Chiller ® Modbus Communication Module ® Air-Cooled Scroll Condensing Unit Air-Cooled Global Screw Air-Cooled Global Scroll Water-Cooled Dual-Compressor Centrifugal, Heat Recovery Water-Cooled Single-Compressor Centrifugal, Heat Recovery Templifier Water Heater ®...
II unit controllers on ® Consult your local Daikin Applied representative for warranty Daikin Applied chillers. It describes how to install or replace details. To find your local Daikin Applied representative, go to a Modbus communication module on a MicroTech II chiller ®...
Agency Listings - Unit Controller to correct the interference at his or her own expense. Daikin disclaims any UL 873 liability resulting from any interference or for the correction thereof.
Introduction Component Data The Modbus communication module is a printed circuit board that inserts directly into the serial card slot of the MicroTech II chiller unit controller as shown in Figure Figure 1: Modbus Communication Module Attached to Unit Controller Modbus Network Connector Figure 2 shows the two important features of the...
Installation Installation and Mounting Installation The following section describes how to field install a new Figure 4: Remove Serial Card Slot Cover Modbus communication module or replace an existing module on the MicroTech II chiller unit controller. CAUTION Electrostatic discharge hazard. Can cause equipment damage.
Page 7
Installation Figure 7: Serial Card Slot Connectors NOTE: This operation relies more on fitting the 8. Mount the plastic cover on the serial card slot. Slip the communication module into the connector than cover over the network connector plug (Figure seeing the connectors mate.
Installation 9. Insert the plug-in connector to the communication Figure 9: Modbus Communication Module Cover module. 10. Replace the cover on the serial card slot. Slip the cover over the network connector plug (Figure 11. Insert the network cable connector into the communication module.
WGZ/TGZ 2001 Modbus. Note: Chiller models AGZ-A/B, ACZ-A/B, WGZ, and TGZ have a single unit NOTE: If using the OITS panel, in the SETPOINTS/MODE controller. Models AGS-B/C and WGS have one unit controller with multiple circuit controllers. Unit settings for AGS-B/C and WGS models are adjusted screen, set the #9 setpoint = to Modbus.
Network Configuration Additional Modbus Configuration Follow these steps to configure the required parameters for the communication module. Refer to Table 2 for default values and Parameters acceptable ranges. The communication module and unit controller support a NOTE: The Network Address (ID or Ident Number), number of Modbus setpoints.
→ Verify the unit controller is set up to communicate Modbus using the keypad/display. Refer to the Network Contact the Daikin Applied Controls Customer Support group Configuration section or the MicroTech II Chiller Unit at 866-462-7829 for additional assistance, if necessary.
Page 12
Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.