Dip Switch Settings - Redback A 4565B Operating Manual

Evacuation controller
Table of Contents

Advertisement

Redback® A 4565B Evacuation Controller

2.4 DIP SWITCH SETTINGS

IMPORTANT NOTE:
Ensure power is switched off when adjusting DIP switches.
New settings will be effective when power is switched back on.
Switches 1-2 Not Used.
Switch 3 Pre-announcement Setting:
DIP switch 3 is used to configure the pre-announcement chime, which is heard when the PTT microphone paging is
activated.
OFF: No pre-announcement chime
ON: Pre announcement chime is activated immediately upon commencement of paging.
Switch 4 Tones Setting:
DIP switch 4 is used to configure the source of the output tones. These can be set to play the MP3 files on the Micro SD
card or revert to the internal Alert, Evac and Bell tones stored on the internal microprocessor.
(Note: No Fire Test or Fire tones are stored internally).
OFF: Output tones set by MP3 files on the Micro SD card.
ON: Output tones set by the internal microprocessor.
(Note: In the ON position the A 4565B will start without the Micro SD card inserted).
Switches 5-8 Evacuation Timer Settings:
These switches control the time period before the unit switches from the alert, to the evac tone (in auto mode). This time
period can be switched from 30s to 7.5 minutes in 30s increments. See fig 2.4 for more information.
Factory preset is set to OFF. When set to OFF the unit will not switch over from the Alert mode to the Evac mode.
5
6
7
8
Fig 2.4
www.redbackaudio.com.au
Redback® Proudly Made In Australia 11

Advertisement

Table of Contents
loading

Table of Contents