Audio Connections - Redback A 4565B Operating Manual

Evacuation controller
Table of Contents

Advertisement

Redback® A 4565B Evacuation Controller

2.3 AUDIO CONNECTIONS

Provision has been made for two different audio sources to be connected to the unit. These are the BGM input and the
Aux input. Both of these inputs have the same priority and are automatically muted when any other function is activated
i.e. Paging, Alert, Evac or Chime triggering.
BGM Input:
This input is for connecting a background music source to the controller. The stereo sockets are combined internally to
form a mono signal. The volume level is set via the BGM level control on the rear of the unit (See Fig 2.3) so that the vol-
ume cannot easily be tampered with.
Aux Input:
This input is for connecting an auxiliary source to the controller for the purposes of background music where the source
volume is required to be accessible from the front panel. The stereo sockets are combined internally to form a mono
signal.
Audio Output:
This output consists of stereo RCA sockets with an output of 0dBm into a 600Ω input. This is suitable for most PA
amplifier auxiliary inputs.
Push
4
6
4
6
2
8
2
8
0
10
0
10
Mic
Aux
Volume
Volume
Hold for 2 seconds
Mic
Aux Volume adjusted via front panel volume control
IMPORTANT NOTE
Ensure power is switched off when
24V DC
24V DC
adjusting DIP switches. New
settings will be effective when
IN
IN
power is switched back on.
DIP Switches
Micro SD Card
1
2
3
4
5
6
7
8
-
+
1 2 3 4 5 6 7 8
(16GB Maximum)
Rear Panel Volume Controls:
The output levels of the Alert, Evac and bell/chime tones can all be adjusted via trimpots located on the rear of the unit.
Volumes are set as follows:
Evac Vol: This sets the output level of the alert & evac tones.
Chime: This sets the output level of the chime.
NOTE: The microphone volume is affected by the tones level. Set this level after setting the tones volume control as the
mic volume is relative to the tones volume. Adjusting the tones volume up will increase the mic volume, and adjusting the
tones volume down will decrease the mic volume.
10
Redback® Proudly Made In Australia
Alert
Evac
Bell
Hold for 2 seconds
Fire
Evac
Alert
Bell
24V Out
24V Out
24V Out
24V Out
Contacts
All switched outputs limited to 120mA maximum current draw
Auto
Cancel
Manual
Isolate
Hold for 2 seconds
REDBACK
TUNER
Aux Music Source
1
2
Common
24V Out
PA Mic
To Wall Plates
To Paging
3
4
Vol
(Maximum 500mA per output)
Console
BGM Volume adjusted
REDBACK
TUNER
Background Music Source
Fig 2.3
A 4565B
Alert/Evac Controller
Mp3
Fire
Fire Test
Error
Active
Active
L
L
R
R
Evac
Bell
Fire
V/Over
Chime
BGM
Audio
Audio
BGM
Vol
Vol
Vol
In
Vol
Vol
Out
Volume
via rear trimpot
www.redbackaudio.com.au
PA
On
Power/
Standby
Active
Made in Australia by
Altronic Distributors
Pty Ltd
L
R
www.redbackaudio.com.au
In

Advertisement

Table of Contents
loading

Table of Contents