Setup

2.10 DIP SWITCH SETTINGS

The A 4500A has various options which are set by the DIP switches on the rear of the unit. These are outlined below and in
figures 2.24 and 2.25.
New settings will be effective when power is switched back on.
Switch 1
This switch is used to either loop the Bell/Prebell, or play the Bell/Prebell only once after it has been triggered.
ON = Loop, OFF = Play Once
Switch 2
DIP switch 2 enables or disables the voice over message. The voice-over message is played in between every three cycles of
the evac tone.
ON = Enabled, OFF = Disabled
Switch 3
This switch can be used to lockout the menu button, to deter tampering with the programmed times.
ON = Menu button disabled, OFF = Menu button enabled
Switch 4
This switch can be used to lockout the front isolate button.
ON = Isolate button disabled, OFF = Isolate button enabled
Switch 5-8 Not Used
SW
1
Loop PreBell/Bell Until Cancelled Play Prebell/Bell Once
3
Disable Menu Options
5-8
2.11 24V OUTPUT CONNECTIONS
These contacts can be used for connection of override relays in remote volume controls, or strobes for unusually noisy envi-
ronments. An override relay is necessary where attenuators are used so that the alert tone, evac tone or message is broadcast
at full volume regardless of the volume setting on the individual volume control (attenuator).
Alert/Evac 24V Out:
These contacts are for switched 24V outputs whenever the alert or evac tones are activated. These may be used to run ex-
ternal systems such as strobes in unusually noisy environments, or override relays in remote volume controls.
When this output becomes active, 24V will appear between the N/O contact and the GND contact. When this output is not
active 24V will appear between the N/C contact and the GND.
Bell 24V Out:
These contacts are for switched 24V outputs whenever the Bell or Relay Only (No MP3 option) are activated These contacts
are for operating an external relay used to operate something like a lunch bell etc.
When this output becomes active, 24V will appear between the N/O contact and the GND contact. When this output is not
active 24V will appear between the N/C contact and the GND.
Common 24V Out:
These contacts are for switched 24V outputs whenever the Alert, Evac, Bell, Prebell or Relay Only (No MP3 option) tones are
activated. When this output becomes active, 24V will appear between the N/O contact and the GND contact. When this
output is not active 24V will appear between the N/C contact and the GND.
www.altronics.com.au
Redback® A 4500A Evac Controller & Timer
IMPORTANT NOTE:
Ensure power is switched off when adjusting DIP switches.
ON
Enable Menu Options
NOT USED
DIP SWITCH SETTINGS
OFF
SW
ON
2
Voice Over Enabled
4
Disable Isolate Switch
Fig 2.24
Redback® Proudly Made In Australia 19
OFF
Voice Over Disabled
Enable Isolate Switch