Table 20 – Temperature Setup Menus
##. #
Temperature Device variable unit
Selection applies digital filtering to
suppress noise effects on the PV.
##. #
The limits for this value are 0.0 to
32.0 seconds
When enabled, adds a constant bias
Enable,
value to the Sensor 2 measured
Disable
value to equate it to the Sensor 1
measured value at the time selected.
When enabled, causes all critical
sensor input failures to latch to the
Critical Fault state. The fault may
Enabled,
only be cleared by device reset.
Disabled
When disabled, the critical sensor
input failure will be cleared if the
input recovers.
Internal,
Determines the source of the Cold
External,
Junction compensation for
Fixed
Thermocouple Sensor types.
When CJ Type is Fixed, specifies
the Cold Junction temperature value
for thermocouple Sensor types.
####.##
Degrees Celsius. Fixed CJ
temperatures below -50 degrees
have no effect on measured values.
mV, TC,
Select Sensor Type1
RTD, Ohm
Sensor ID for
Select Sensor ID for Input n for
Input 1
selected Sensor Type.
2-Wire, 3-
Select the RTD Type per the
Wire, 4-Wire
number of lead wires
Resistance valve of the sensor lead
####.##
wire
####.##
Bias on the measured value
The limit for the Lower Range Value is the Lower
Range Limit (LRL) of the selected Sensor ID.
The limit for the Upper Range Value is the Upper
Range Limit (URL) of the selected Sensor ID.
ATTENTION: Executing this service will set the
Lower Range Value (LRV) equal to the Input 1
measurement
ATTENTION: Executing this service will set the
Upper Range Value (URV) equal to the Input 1
measurement
SMV800 Transmitter User's Manual
Press  to
enter menu
selection
 and  to
select
Alphanumeric
 to enter
and shift to
next
character to
the right.
Press ↵ to
enter menu
selection
↑ and ↓ to
select entry.
↵ to enter
Press  to
enter menu
selection
 to execute