Setting BSC Mode
1. Set the master BSC system. On the main menu of the LCDs of the UPS, choose System Info >
Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC
mode to BSC master mode.
2. Set the slave BSC system. On the main menu of the LCDs of the UPS, choose System Info >
Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC
mode to BSC slave mode.
3. If no alarm is generated after settings, the UPS runs properly.
The default value of BSC mode is Non-BSC. Set it to BSC mode when the system is a dual-
bus system.
The dual-bus system consists of one master and one slave BSC system. You can specify one
master and one slave BSC system during initial startup and change the settings under the
guidance of maintenance engineers. Set the master and slave BSC systems to master and
slave BSC modes respectively.
Ensure that the BSC signal cable between the master and slave BSC systems is properly
connected and that BSC-related hardware is properly installed.