Checkout Procedure - Simplex 4606-9102 Installation Instructions Manual

Annunciator for 4010es lcd

Advertisement

4606-9102 LCD Annunciator installation instructions
Wire length
tables
Total Current
(Amps)
0.100
0.200
Table 4: Without 2081-9044 / 2081-9027 Circuit Protectors (or with 2081-9028 Circuit
Total
Current
(Amps)
0.100
0.200
0.300
0.400
0.500
0.600
0.700
0.800
0.900
1.000
1.100
1.200
0.100
0.200
Communication line tables:
12 AWG (3.309 mm²)
2,500ft (762m)
Table 6: Without 2081-9044 / 2081-9027 Circuit Protectors (or with 2081-9028 Circuit Protectors)
12 AWG (3.309 mm²)
2,500ft (762m)
2,500ft (762m)
Checkout
When the installation is complete, verify that the remote annunciator is working correctly:
procedure
1. Verify that the LEDs and the LCD are working by turning the keyswitch OFF and then ON. This
process causes the remote annunciator to execute a self-test which checks each LED and the
LCD.
2. Verify that the annunciator communicates properly with the FACU by observing the remote
annunciator. If the annunciator is not wired properly and is not communicating with the FACU,
error messages are displayed and an audible signal is emitted. Also, a card missing trouble is
displayed at the FACU.
Note: For Programming changes, refer to the relevant panel programming manual.
Table 3: With 2081-9044 or 2081-9027 Circuit Protectors
12 AWG
14 AWG
(3.309 mm²)
(2.801 mm²)
2,500ft (762m)
2,500ft (762m)
2,500ft (762m)
1,782ft (543.15m)
12 AWG
14 AWG
(3.309 mm²)
(2.801 mm²)
2,500ft (762m)
2,500ft (762m)
2,500ft (762m)
2,500ft (762m)
2,500ft (762m)
1,980ft (603.5m)
2,361ft (719.63m)
1,485ft (452.62m)
1,889ft (575.76m)
1,188ft (362.1m)
1,574ft (479.75m)
990ft (301.75m)
1,349ft (411.17m)
849ft (258.77m)
1,181ft (359.96m)
743ft (226.46m)
1,049ft (319.73m)
660ft (201.16m)
944ft (287.73m)
594ft (181.05m)
859ft (261.82m)
540ft (164.59m)
787ft (239.87m)
495ft (150.87m)
With 2081-9027 isolated Loop Circuit Protectors
2,500ft (762m)
2,500ft (762m)
2,500ft (762m)
1,782ft (543.15m)
Table 5: With 2081-9044 or 2081-9027 Circuit Protectors
14 AWG (2.801 mm²)
2,500ft (762m)
14 AWG (2.801 mm²)
2,500ft (762m)
With 2081-9027 isolated Loop Circuit Protectors
2,500ft (762m)
16 AWG
(1.309 mm²)
2,371ft (722.68m)
889ft (270.96m)
Protectors)
16 AWG
(1.309 mm²)
2,500ft (762m)
1,482ft (451.71m)
988ft (301.14m)
741ft (225.85m)
593ft (180.74m)
494ft (150.57m)
423ft (128.93m)
371ft (113.08m)
329ft (100.27m)
296ft (90.22m)
269ft (81.99m)
247ft (75.28m)
2,371ft (722.68m)
889ft (270.96m)
16 AWG (1.309 mm²)
2,450ft (746.76m)
16 AWG (1.309 mm²)
2,500ft (762m)
2,450ft (746.76m)
18 AWG
(0.823 mm²)
1,409ft (429.46m)
705ft (214.88m)
18 AWG
(0.823 mm²)
2,349ft (715.97m)
1,175ft (358.14m)
783ft (238.65m)
587ft (178.91m)
470ft (143.25m)
392ft (119.48m)
336ft (102.41m)
294ft (89.61m)
261ft (79.55m)
235ft (71.62m)
214ft (65.22m)
196ft (59.74m)
1,409ft (429.46m)
705ft (214.88m)
18 AWG (0.823 mm²)
1,650ft (502.92m)
18 AWG (0.823 mm²)
2,500ft (762m)
1,650ft (502.92m)
579-977
Rev. C