Warnings
11.
Accessing the Expert menu and Emergency mode
To access the Expert menu:
Menu
11.1. Electric backup
See section "6.1.3. Electric backup", page 103.
11.2. Anti-Legionella function
This menu is used to set the cycle frequency and setpoint (62 °C or 65 °C or 70 °C).
If the anti-Legionella function mode has been activated, the product will heat up to a raised
setpoint during an active period.
11.3. External control
See section "6.1.1. External control", page 101.
11.4. Diagnostics and checking operation
This menu is used to access the alarm log, the system data (hot water temperature, heat
pump, heat pump status, etc.) and the test mode. The test mode is used to check that the
water heater is operating correctly.
•
Heat pump heating mode: outside unit starts up with water heating
•
Heat pump cooling mode: outside unit starts in cooling mode to perform pump down
•
Electric backup: Commissioning of the electric backup
In the H.P heating mode test mode, the heat pump starts 3 minutes after powering on only
if the following conditions are met:
•
water temperature at the top of the tank less than 60 °C;
•
air temperature between -10 °C and 37 °C;
•
no limitation on the heat pump (high pressure, current, etc.)
Otherwise, start the heat pump (cooling mode) to check that it is operating correctly.
108
108
Installation
Parameters
Use
Expert access