Q5Z Global Laser Measurement Sensor With IO-Link Instruction Manual
Chapter Contents
4.1 Reset to Factory Defaults Using the Remote Input ..................................................................................................................................... 15
Chapter 4
Use the remote input to program the sensor remotely.
Remote input is available when the Channel 2 Function is configured to Remote TEACH input.
The remote input provides limited programming options and is configured to be Active High (PNP).
For Active High (PNP), connect the white wire to 24 V DC with a remote switch connected between the wire and 24 V DC.
Pulse the remote input according to the diagram and the instructions provided in this manual.
The length of the individual programming pulses is equal to the value T: 0.04 seconds ≤ T ≤ 0.8 seconds.
Exit remote programming modes by activating the remote input for longer than 2 seconds.
Remote Input Map
Figure 17.
Input Wire Function = Set
Remote
Remote TEACH input per
Input
wiring diagram
1x
8x
Reset to Factory Defaults Using the Remote Input
4.1
Follow the instructions below to reset the Q5Z Global to factory defaults using Remote Input.
Eightpulse the remote input to apply the factory defaults and return to Run mode.
NOTE: The input wire function remains at remote teach input.
June 23, 2023
Remote Input
0.04 seconds < T < 0.8 seconds
Timing between Pulse groups > 1 second
Starts selected Teach (same function as pressing Teach Button for > 2 sec)
Second pulse completes Teach (Two-point, Dynamic Teach and Dual Mode only)
1x
Reset to Factory Defaults (maintain remote input = SET)
T
T